Product Technical Guides : US-EN Anchor Fastening - August 2021 | Page 374

Table 9 — Hilti KWIK HUS-EZ I and KWIK HUS-EZ E in the soffit of uncracked lightweight concrete over metal deck 1 , 2 , 3 , 4 , 5 , 6
Nominal anchor diameter in .
1 / 4
3 / 8
Nominal internal thread diameter in .
1 / 4-20 UNC
3 / 8-16 UNC
Nominal embed . depth in . ( mm ) ƒ ' c
= 3,000 psi ( 20.7 MPa ) lb ( kN )
Installation in lower flute Installation in upper flute
Tension - фN n Shear - фV n
Tension - фN n Shear - фV n ƒ ' c
= 4,000 psi ( 27.6 MPa ) lb ( kN ) ƒ ' c
= 3,000 psi ( 20.7 MPa ) lb ( kN ) ƒ ' c
= 4,000 psi ( 27.6 MPa ) lb ( kN ) ƒ ' c
= 3,000 psi ( 20.7 MPa ) lb ( kN ) ƒ ' c
= 4,000 psi ( 27.6 MPa ) lb ( kN ) ƒ ' c
= 3,000 psi ( 20.7 MPa ) lb ( kN ) ƒ ' c
= 4,000 psi ( 27.6 MPa ) lb ( kN )
1-5 / 8 545 595 515 515 670 730 610 610 ( 41 ) ( 2.4 ) ( 2.6 ) ( 2.3 ) ( 2.3 ) ( 3.0 ) ( 3.2 ) ( 2.7 ) ( 2.7 ) 2-1 / 2 1,220 1,410 515 515 1,275 1,470 610 610 ( 64 ) ( 5.4 ) ( 6.3 ) ( 2.3 ) ( 2.3 ) ( 5.7 ) ( 6.5 ) ( 2.7 ) ( 2.7 ) 1-5 / 8 545 595 615 615 670 730 915 915 ( 41 ) ( 2.4 ) ( 2.6 ) ( 2.7 ) ( 2.7 ) ( 3.0 ) ( 3.2 ) ( 4.1 ) ( 4.1 ) 2-1 / 2 1,220 1,410 615 615 1,275 1,470 915 915 ( 64 ) ( 5.4 ) ( 6.3 ) ( 2.7 ) ( 2.7 ) ( 5.7 ) ( 6.5 ) ( 4.1 ) ( 4.1 ) 1 / 2-13 2-1 / 8 1,120 1,295 1,430 1,430 1,730 2,000 2,190 2,190 UNC ( 54 ) ( 5.0 ) ( 5.8 ) ( 6.4 ) ( 6.4 ) ( 7.7 ) ( 8.9 ) ( 9.7 ) ( 9.7 )
Table 10 — Hilti KWIK HUS-EZ I and KWIK HUS-EZ E in the soffit of cracked lightweight concrete over metal deck 1 , 2 , 3 , 4 , 5 , 6 , 7 , 8
Nominal anchor diameter in .
1 / 4
3 / 8
Nominal internal thread diameter in .
1 / 4-20 UNC
3 / 8-16 UNC
Nominal embed . depth in . ( mm ) ƒ ' c
= 3,000 psi ( 20.7 MPa ) lb ( kN )
Installation in lower flute Installation in upper flute
Tension - фN n Shear - фV n
Tension - фN n Shear - фV n ƒ ' c
= 4,000 psi ( 27.6 MPa ) lb ( kN ) ƒ ' c
= 3,000 psi ( 20.7 MPa ) lb ( kN ) ƒ ' c
= 4,000 psi ( 27.6 MPa ) lb ( kN ) ƒ ' c
= 3,000 psi ( 20.7 MPa ) lb ( kN ) ƒ ' c
= 4,000 psi ( 27.6 MPa ) lb ( kN ) ƒ ' c
= 3,000 psi ( 20.7 MPa ) lb ( kN ) ƒ ' c
= 4,000 psi ( 27.6 MPa ) lb ( kN )
1-5 / 8 280 305 515 515 330 360 610 610 ( 41 ) ( 1.2 ) ( 1.4 ) ( 2.3 ) ( 2.3 ) ( 1.5 ) ( 1.6 ) ( 2.7 ) ( 2.7 ) 2-1 / 2 605 700 515 515 635 735 610 610 ( 64 ) ( 2.7 ) ( 3.1 ) ( 2.3 ) ( 2.3 ) ( 2.8 ) ( 3.3 ) ( 2.7 ) ( 2.7 ) 1-5 / 8 280 325 615 615 330 380 915 915 ( 41 ) ( 1.2 ) ( 1.4 ) ( 2.7 ) ( 2.7 ) ( 1.5 ) ( 1.7 ) ( 4.1 ) ( 4.1 ) 2-1 / 2 605 700 615 615 635 735 915 915 ( 64 ) ( 2.7 ) ( 3.1 ) ( 2.7 ) ( 2.7 ) ( 2.8 ) ( 3.3 ) ( 4.1 ) ( 4.1 ) 1 / 2-13 2-1 / 8 795 920 1,430 1,430 1,225 1,415 2,190 2,190 UNC ( 54 ) ( 3.5 ) ( 4.1 ) ( 6.4 ) ( 6.4 ) ( 5.4 ) ( 6.3 ) ( 9.7 ) ( 9.7 )
1 See Section 3.1.8 to convert design strength value to ASD value . 2 Linear interpolation between embedment depths and concrete compressive strengths is not permitted . 3 Tabular value is for one anchor per flute . Minimum spacing along the length of the flute is 3 x h nom
( nominal embedment ).
4 Tabular values are lightweight concrete and no additional reduction factor is needed . 5 No additional reduction factors for spacing or edge distance need to be applied . 6 Comparison of the tabular values to the steel strength is not necessary . Tabular Values control . 7 Tabular values are for static loads only . For seismic tenison loads , multiply cracked concrete tabular values in tension by α N , seis
= 0.75 .
8 For seismic shear , an additional factor must be applied to the cracked concrete tabular values for seismic conditions : 1 / 4-in diameter by 1-5 / 8-in nominal embedment depth - α V , seis
= 0.44
1 / 4-in diameter by 2-1 / 2-in nominal embedment depth - α V , seis
= 0.85 See Section 3.1.8 for additional information on seismic applications .
370 Anchor Fastening Technical Guide Edition 22 | 3.0 ANCHORING SYSTEMS | 3.3.8 KWIK HUS-EZ I AND KWIK HUS-EZ E CARBON STEEL SCREW ANCHOR Hilti , Inc . 1-800-879-8000 | en español 1-800-879-5000 | www . hilti . com | Hilti ( Canada ) Corporation | www . hilti . ca | 1-800-363-4458