Post-Installed Anchors in Masonry US English | Page 20

Table 4 — Hilti HIT-HY 200 V3 adhesive design strength with masonry / bond failure for threaded rod in the face of uncracked fully grouted CMU walls and installed at minimum distance from centerline of hollow head joint 1 , 2 , 3 , 4 , 5 , 6 , 7 , 8
Nominal anchor diameter in .
3 / 8
1 / 2
5 / 8
3 / 4
Effective embedment in . ( mm ) f ́m = 1500 psi ( 10.3 MPa ) lb ( kN )
Tension ( lesser of breakout or bond ) — ΦN n
f ́m = 2000 psi ( 13.8 MPa ) lb ( kN ) f ́m = 2500 psi ( 17.2 MPa ) lb ( kN ) f ́m = 3000 psi ( 20.7 MPa ) lb ( kN )
Shear ( lesser of breakout , pryout , or crushing ) — ΦV n
f ́m = 1500 psi ( 10.3 MPa ) lb ( kN ) f ́m = = 2000 psi ( 13.8 MPa ) lb ( kN ) f ́m = 2500 psi ( 17.2 MPa ) lb ( kN ) f ́m = 3000 psi ( 20.7 MPa ) lb ( kN )
2-3 / 8
1,010
1,120
1,120
1,120
1,085
1,210
1,210
1,210
( 60 )
( 4.5 )
( 5.0 )
( 5.0 )
( 5.0 )
( 4.8 )
( 5.4 )
( 5.4 )
( 5.4 )
4-1 / 2
2,025
2,125
2,125
2,125
1,205
1,390
1,555
1,700
( 114 )
( 9.0 )
( 9.5 )
( 9.5 )
( 9.5 )
( 5.4 )
( 6.2 )
( 6.9 )
( 7.6 )
6-3 / 4
3,185
3,185
3,185
3,185
1,205
1,390
1,555
1,700
( 171 )
( 14.2 )
( 14.2 )
( 14.2 )
( 14.2 )
( 5.4 )
( 6.2 )
( 6.9 )
( 7.6 )
7-1 / 2
3,540
3,540
3,540
3,540
1,205
1,390
1,555
1,700
( 191 )
( 15.7 )
( 15.7 )
( 15.7 )
( 15.7 )
( 5.4 )
( 6.2 )
( 6.9 )
( 7.6 )
2-3 / 4
1,170
1,350
1,510
1,650
1,290
1,490
1,665
1,825
( 70 )
( 5.2 )
( 6.0 )
( 6.7 )
( 7.3 )
( 5.7 )
( 6.6 )
( 7.4 )
( 8.1 )
4-1 / 2
2,025
2,335
2,610
2,730
1,390
1,605
1,795
1,965
( 114 )
( 9.0 )
( 10.4 )
( 11.6 )
( 12.1 )
( 6.2 )
( 7.1 )
( 8.0 )
( 8.7 )
6-3 / 4
3,335
3,850
4,100
4,100
1,390
1,605
1,795
1,965
( 171 )
( 14.8 )
( 17.1 )
( 18.2 )
( 18.2 )
( 6.2 )
( 7.1 )
( 8.0 )
( 8.7 )
10
5,585
6,070
6,070
6,070
1,390
1,605
1,795
1,965
( 254 )
( 24.8 )
( 27.0 )
( 27.0 )
( 27.0 )
( 6.2 )
( 7.1 )
( 8.0 )
( 8.7 )
3-1 / 8
1,340
1,545
1,725
1,880
1,415
1,635
1,825
2,000
( 79 )
( 6.0 )
( 6.9 )
( 7.7 )
( 8.4 )
( 6.3 )
( 7.3 )
( 8.1 )
( 8.9 )
4-1 / 2
2,025
2,335
2,610
2,710
1,520
1,755
1,965
2,150
( 114 )
( 9.0 )
( 10.4 )
( 11.6 )
( 12.1 )
( 6.8 )
( 7.8 )
( 8.7 )
( 9.6 )
6-3 / 4
3,335
3,850
4,065
4,065
1,555
1,795
2,005
2,195
( 171 )
( 14.8 )
( 17.1 )
( 18.1 )
( 18.1 )
( 6.9 )
( 8.0 )
( 8.9 )
( 9.8 )
10
5,585
6,020
6,020
6,020
1,555
1,795
2,005
2,195
( 254 )
( 24.8 )
( 26.8 )
( 26.8 )
( 26.8 )
( 6.9 )
( 8.0 )
( 8.9 )
( 9.8 )
3-1 / 2
1,515
1,750
1,955
2,140
1,530
1,765
1,975
2,160
( 89 )
( 6.7 )
( 7.8 )
( 8.7 )
( 9.5 )
( 6.8 )
( 7.9 )
( 8.8 )
( 9.6 )
4-1 / 2
2,025
2,335
2,610
2,860
1,605
1,855
2,075
2,270
( 114 )
( 9.0 )
( 10.4 )
( 11.6 )
( 12.7 )
( 7.1 )
( 8.3 )
( 9.2 )
( 10.1 )
6-3 / 4
3,335
3,850
4,305
4,525
1,665
1,925
2,150
2,360
( 171 )
( 14.8 )
( 17.1 )
( 19.1 )
( 20.1 )
( 7.4 )
( 8.6 )
( 9.6 )
( 10.5 )
10
5,585
6,450
6,705
6,705
1,665
1,925
2,150
2,360
( 254 )
( 24.8 )
( 28.7 )
( 29.8 )
( 29.8 )
( 7.4 )
( 8.6 )
( 9.6 )
( 10.5 )
1 Linear interpolation between embedment depths and masonry compressive strengths is not permitted .
2 Tabular values are for a single anchor located 2-in from centerline of a hollow head joint with no additional influence from nearby edges or additional anchors . For designs with the influence of nearby edges , different distances to a hollow head joint , or additional anchors , use Hilti PROFIS Engineering Design software or perform anchor calculation using design equations from AC58 . 3 Compare masonry tabular values to the steel values in the Appendix . The lesser of the values is to be used for the design . 4 The maximum embedment for a 8-in CMU block is 6-3 / 4-in . The maximum embedment for a 10-in CMU block is 8-in . The maximum embedment for a 12-in CMU block is 10-in . 5 Data is for Temperature Range A : Maximum short term temperature = 130 ° F ( 55 ° C ) | Maximum long term temperature = 110 ° F ( 43 ° C ).
For Temperature Range B : Maximum short term temperature = 176 ° F ( 80 ° C ) | Maximum long term temperature = 110 ° F ( 43 ° C ), multiply design strength values by 0.82 . 6 Tabular values are for dry masonry conditions . For water saturated masonry conditions , multiply design strength values by α sat
3 / 8-in diameter - α sat = 1.00
1 / 2-in diameter - α sat = 0.93
5 / 8-in diameter - α sat = 0.79
3 / 4-in diameter - α sat
= 0.65 7 Tabular values are for static loads only . Seismic design is not permitted for uncracked masonry . 8 Tabular values are for short term loads only . For sustained loads including overhead use , see Section 3.0 .
20 Masonry Fastening Technical Guide Edition 24 | 7.0 HIT-HY 200 V3 HYBRID FOR MASONRY CONSTRUCTION Hilti , Inc . 1-800-879-8000 | en español 1-800-879-5000 | www . hilti . com | Hilti ( Canada ) Corporation | www . hilti . ca | 1-800-363-4458