TECHNICAL 53 Table 3: primary circulation loop pipes and fittings, the type and quality of which shall comply with requirements of SANS 10252-1. 4.1.3.3 An approved air source water heating heat pump unit shall be used. 4.1.3.4 The storage water heater shall comply with SANS 151. 4.1.3.5 Drain valves for water heaters shall comply with SANS 1808-53. 4.1.3.6 All pressure control valves, expansion control valves. Safety valve (temperature and pressure control) and vacuum control valves, shall comply with SANS 198. Municipal by-laws: Technical requirements for a water installation 39 (1) Notwithstanding the requirement that a certificate be March 2020 Volume 26 I Number 01 issued in terms of section 36(3)(c), water installations must comply with SABS Code 0252 Part 1 and all fixed electrical storage water heaters must comply with SABS Code 0254. A very high proportion (perhaps as much as 90%) of municipalities have similar requirements. The municipal water by-laws and SANS documents require that the storage water heater must comply with SANS 151, and do not mention class B requirements. The current SANS 151 does not have a pass/fail criteria of class B, but a lower standing loss requirement in Table 3. VC 9006 has two requirements, namely that storage water heaters must comply with both SANS 151 and Class B. Therefore, the VC requirements are contradictory until SANS 151 standing loss requirements are changed to accommodate Class B requirements. This means suppliers and installers that do not have the necessary documentary evidence will be at risk of prosecution by the NCRS. PA www.plumbingafrica.co.za