Modular Pipe Shoes Technical Supplement
5.0 PIPE SHOE GUIDE 5.1 MT-FPS-S 5.1.2 MT-FPS-SZ1
• 2 brackets = SZ1 connector each side of base for 1-1 configuration as shown
Table 44 : MT-FPS-SZ1 Allowable Design Strength ( ASD ) Load Data per MSS SP-58 1 , 2 , 3 , 4
Configuration
2 Brackets
+/ -Fy lb ( kN )
360 / H center ( 1.61 / H center
)
-Fz lb ( kN )
980 ( 4.36 )
1 Tabulated directional values apply separately in each direction . A combination of loads must be considered separately , and an appropriate interaction equation defined by the design professional must be applied . 2 MSS SP-58 values are based off the safety factors provided in the MSS SP-58 . 3 Tabulated values as shown does not include or account for anchorage . Anchorage must be determined separately and may reduce the overall capacity from the tabulated values . 4 H Center units are in inches .
Table 45 : MT-FPS-SZ1 Allowable Design Strength ( ASD ) Load Data 1 , 2 , 3 , 4
Configuration
2 Brackets
+/ -Fy lb ( kN )
1180 / H center ( 5.25 / H center
)
-Fz lb ( kN )
340 ( 1.51 )
1 Tabulated directional values apply separately in each direction . A combination of loads must be considered separately , and an appropriate interaction equation defined by the design professional must be applied .
2 Tabulated values as shown does not include or account for anchorage . Anchorage must be determined separately and may reduce the overall capacity from the tabulated values . 3 Multiply tabulated values by 1.5 to convert SD values to Design Strength ( LRFD ). 4 H Center units are in inches .
Table 46 : MT-FPS-SZ1 Limit State Design ( LSD ) Load Data 1 , 2 , 3
Configuration
2 Brackets
+/ -Fy lb ( kN )
1020 / H center ( 4.54 / H center
)
-Fz lb ( kN )
420 ( 1.87 )
Fy Fx
1 Tabulated directional values apply separately in each direction . A combination of loads must be considered separately , and an appropriate interaction equation defined by the design professional must be applied .
2 Tabulated values as shown does not include or account for anchorage . Anchorage must be determined separately and may reduce the overall capacity from the tabulated values .
3 H Center units are in inches .
Fz
2023
48