Modular Pipe Shoes Technical Supplement
2.0 PIPE SHOE MP-PS 2.1 MP-PS 1-1
Table 7 : MP-PS 1-1 Limit State Design ( LSD ) Load Data 1 , 2 ( continued )
Order designation
+/ -Fx lb ( kN )
High MP-PS 1-1
+/ -Fy lb ( kN )
+ Fz lb ( kN )
-Fz lb ( kN )
MP-PS H1-1 21-26 1 / 2 " OC 411 ( 1.83 ) 430 ( 1.91 ) 2900 ( 12.9 ) 2230 ( 9.92 ) MP-PS H1-1 26-31 3 / 4 " OC 427 ( 1.9 ) 430 ( 1.91 ) 2900 ( 12.9 ) 2230 ( 9.92 ) MP-PS H1-1 32-37 1 " OC 447 ( 1.99 ) 420 ( 1.87 ) 2900 ( 12.9 ) 2230 ( 9.92 ) MP-PS H1-1 38-44 1-1 / 4 " OC 474 ( 2.11 ) 410 ( 1.82 ) 2900 ( 12.9 ) 2230 ( 9.92 ) MP-PS H1-1 45-51 1-1 / 2 " OC 492 ( 2.19 ) 410 ( 1.82 ) 2900 ( 12.9 ) 2230 ( 9.92 ) MP-PS H1-1 52-58 OC 508 ( 2.26 ) 400 ( 1.78 ) 2900 ( 12.9 ) 2230 ( 9.92 ) MP-PS H1-1 59-65 2 " OC 526 ( 2.34 ) 400 ( 1.78 ) 2900 ( 12.9 ) 2230 ( 9.92 ) MP-PS H1-1 68-74 OC 555 ( 2.47 ) 390 ( 1.73 ) 2900 ( 12.9 ) 2230 ( 9.92 ) MP-PS H1-1 75-81 2-1 / 2 " OC 564 ( 2.51 ) 380 ( 1.69 ) 2900 ( 12.9 ) 2230 ( 9.92 ) MP-PS H1-1 88-94 3 " OC 611 ( 2.72 ) 370 ( 1.65 ) 2900 ( 12.9 ) 2230 ( 9.92 ) MP-PS H1-1 100-108 3-1 / 2 " OC 650 ( 2.89 ) 360 ( 1.6 ) 2900 ( 12.9 ) 2230 ( 9.92 ) MP-PS H1-1 110-118 4 " OC 688 ( 3.06 ) 350 ( 1.56 ) 2900 ( 12.9 ) 2230 ( 9.92 ) MP-PS H1-1 125-133 OC 719 ( 3.2 ) 350 ( 1.56 ) 2900 ( 12.9 ) 2230 ( 9.92 ) MP-PS H1-1 136-144 5 " OC 767 ( 3.41 ) 340 ( 1.51 ) 2900 ( 12.9 ) 2230 ( 9.92 ) MP-PS H1-1 152-162 OC 821 ( 3.65 ) 330 ( 1.47 ) 2900 ( 12.9 ) 2230 ( 9.92 ) MP-PS H1-1 163-173 6 " OC 848 ( 3.77 ) 320 ( 1.42 ) 2900 ( 12.9 ) 2230 ( 9.92 )
1 Tabulated directional values apply separately in each direction . A combination of loads must be considered separately , and an appropriate interaction equation defined by the design professional must be applied .
2 Tabulated values as shown does not include or account for anchorage . Anchorage must be determined separately and may reduce the overall capacity from the tabulated values .
FY
FX
FZ-
FZ +
Pipe Axis
2023
19