Modular Pipe Shoes Technical Supplement
2.0 PIPE SHOE MP-PS 2.1 MP-PS 1-1
Table 5 : MP-PS 1-1 Allowable Strength Design ( ASD ) Load Data per MSS SP-58 1 , 2 , 3 ( continued )
Order designation
+/ -Fx lb ( kN )
High MP-PS 1-1
+/ -Fy lb ( kN )
+ Fz lb ( kN )
-Fz lb ( kN )
MP-PS H1-1 21-26 1 / 2 " OC 267 ( 1.19 ) 290 ( 1.29 ) 1540 ( 6.85 ) 1190 ( 5.29 ) MP-PS H1-1 26-31 3 / 4 " OC 278 ( 1.24 ) 280 ( 1.25 ) 1540 ( 6.85 ) 1190 ( 5.29 ) MP-PS H1-1 32-37 OC 293 ( 1.3 ) 280 ( 1.25 ) 1540 ( 6.85 ) 1190 ( 5.29 ) MP-PS H1-1 38-44 1-1 / 4 " OC 311 ( 1.38 ) 270 ( 1.2 ) 1540 ( 6.85 ) 1190 ( 5.29 ) MP-PS H1-1 45-51 1-1 / 2 " OC 324 ( 1.44 ) 270 ( 1.2 ) 1540 ( 6.85 ) 1190 ( 5.29 ) MP-PS H1-1 52-58 OC 336 ( 1.49 ) 270 ( 1.2 ) 1540 ( 6.85 ) 1190 ( 5.29 ) MP-PS H1-1 59-65 2 " OC 349 ( 1.55 ) 260 ( 1.16 ) 1540 ( 6.85 ) 1190 ( 5.29 ) MP-PS H1-1 68-74 OC 370 ( 1.65 ) 260 ( 1.16 ) 1540 ( 6.85 ) 1190 ( 5.29 ) MP-PS H1-1 75-81 2-1 / 2 " OC 376 ( 1.67 ) 260 ( 1.16 ) 1540 ( 6.85 ) 1190 ( 5.29 ) MP-PS H1-1 88-94 3 " OC 410 ( 1.82 ) 250 ( 1.11 ) 1540 ( 6.85 ) 1190 ( 5.29 ) MP-PS H1-1 100-108 3-1 / 2 " OC 436 ( 1.94 ) 240 ( 1.07 ) 1540 ( 6.85 ) 1190 ( 5.29 ) MP-PS H1-1 110-118 4 " OC 463 ( 2.06 ) 240 ( 1.07 ) 1540 ( 6.85 ) 1190 ( 5.29 ) MP-PS H1-1 125-133 OC 486 ( 2.16 ) 230 ( 1.02 ) 1540 ( 6.85 ) 1190 ( 5.29 ) MP-PS H1-1 136-144 5 " OC 520 ( 2.31 ) 220 ( 0.98 ) 1540 ( 6.85 ) 1190 ( 5.29 ) MP-PS H1-1 152-162 OC 557 ( 2.48 ) 220 ( 0.98 ) 1540 ( 6.85 ) 1190 ( 5.29 ) MP-PS H1-1 163-173 6 " OC 577 ( 2.57 ) 210 ( 0.93 ) 1540 ( 6.85 ) 1190 ( 5.29 )
1 Tabulated directional values apply separately in each direction . A combination of loads must be considered separately , and an appropriate interaction equation defined by the design professional must be applied . 2 MSS SP-58 values are based off the safety factors provided in the MSS SP-58 . 3 Tabulated values as shown does not include or account for anchorage . Anchorage must be determined separately and may reduce the overall capacity from the tabulated values .
FY
FX
FZ-
FZ +
Pipe Axis
2023
15