FLOAT AND FLOW CONTROLS F262 MECHANICAL LIQUID FLOW SWITCH
TECHNICAL SPECIFICATIONS
UL CONFORMITY DECLARATION INFORMATION
Purpose of control F262 Series Airflow Switch
Construction of control Electronic independently mounted control
Number of cycles
100,000 cycles Method of mounting control Mounting to sensed media vessel / orientation Type 1 or type 2 action Type 1 . C ( Microinterruption ) External pollution situation Pollution degree 4 Internal pollution situation Pollution degree 2 Rated impulse voltage
4,000 VAC
Ball pressure temperature Enclosure 130 ° C
Switch component 122 ° C Control adjustment instruction --- Field wiring rating Wire / Cord temperature ratings : 60 ° C only permitted when ambient air and media are less than 45 ° C 75 ° C only permitted when ambient air and media are less than 60 ° C 90 ° C only permitted when ambient air is less than 60 ° C and media is less than 75 ° C 150 ° C permitted when ambient air is less than 60 ° C and media is less than 121 ° C