PECM Issue 34 2018 | Page 110

SHOCK PROTECTION ELECTRICAL & ELECTRONICS DOEPKE BS7671 18TH EDITION REVISED RCD REQUIREMENTS If you are involved in the safety specification and or installation of electrical equipment, take note of changes that will come into force in BS7671 January 2019 (18th Edition). There are a number of recommendations directly linked to improving the security and safety of electrical installations protected by RCDs. Why is BS7671 relevant to most industrial sites? The Electricity at Work Regulations and the HSE refer to BS7671 as a “Code of Practice” for electrical installation”. Circuits may rely on additional protection provide by RCDs, to reduce deaths from electrocution and or fire. Installations using Type AC RCDs may not provide the level of protection required, when supplying modern equipment containing switch mode power supplies and inverters. The 18th Edition Regs specify the Type of RCD required, based on the types of residual current generated by the equipment connected to the supply see 531.3.3 and Annex A53 Fig A53. This is a general requirement and applies to all installations. Particular requirements see Part 7. 531.3.3 Types of RCD The type of RCD installed must be capable of providing the required level of protection based on the residual currents that may be generated under possible fault conditions: “Different types of RCD exist, depending on their behaviour in the presence of DC components and frequencies. The appropriate RCD shall be selected from the following”, this clause goes on to list the various types of RCD namely A, F, B and their suitability for different types of residual current. Type AC RCDs are only listed for general purpose applications such as electric kettles, emersion heaters, filament lamps. Many modern appliances contain semiconductors, and are not suitable for connection to Type AC RCDs e.g. The internal topology of a Single phase VFD/ VSD will determine the residual current characteristics (Type A, F or B) and therefore the type of RCDs that can be installed safely upstream. 3 phase VFD/VSD must only be connected to Type B RCDs, irrespective of the application or location. 110 PECM Issue 34 Two examples of possible fault currents in circuits containing semiconductor devices (PECS): see BS7671 Annex A53 Fig A53.1 Circuit with fault location Normal load current I L L ~ I L I L 50Hz RCD Type Earth fault current I F I F t t "A" I F N PE Example 1. Phase control: I F frequency is the same as the supply current I L @ 50Hz I F1 I L L I L ~ M 50Hz N PE t t I F2 = I F1 "F, B" t I F2 Example 2. Inverter control: I F2 frequency is a function of the Inverter / Motor design>>50Hz doepke cla 07/17 Annex A53.1 gives details of typical faults currents associated with circuits containing semiconductors and the required RCD type (see example 1 and 2). These recommendations along with other changes are directly linked to reducing the risks associated with electrical faults, namely fire and electrocution. For additional information on RCDs refer to www.doepke.co.uk/ download/Techpub-16