Modular Supports System Product Technical Guide June 2026 | Page 81

Modular Support Systems Technical Guide, Edition 2
3.0 Modular Support System
3.2.2 MT Base Connectors
MT-B-O2
Description
2-hole base plate intended to be installed with a Twist- Lock and Twist-Lock bolt for channel-to-concrete or channel-to-steel( X-BT / S-BT / F-BT compatible).
Material Specifications
Standard 1 Grade 1 F y, ksi( MPa) F u, ksi( MPa) GB / T 700 Q235 B 34.08( 235) 53.66( 370)
1 Mechanical properties of GB / T 700 Grade Q235 B meet or exceed the mechanical properties of ASTM A1011 SS Grade 33.
Corrosion Protection
Description
Environmental Conditions
MT-B-O2
Dry indoor conditions( C1)
Indoor with temporary condensation( C2)
MT-B-O2 OC
Outdoor, low to moderate pollution( C3 / C4- low)
Ordering Information
Description
Weight Per Piece, lbs( kg)
Quantity Piece( s)
Item No. MT-B-O2 2.27( 1.03) 12 2272094 MT-B-O2 OC 2.27( 1.03) 12 2272096 mm( in)
Figure 15 – MT Concentric Channel Connection
Table 132- Allowable Strength Design( ASD) Load Data 1, 2, 3, 4
Fx lb( kN)
Fy lb( kN)
Fz lb( kN)
My lb ft( kN m)
2,105( 9.38)
350( 1.56)
980( 4.36)
720( 0.98)
1 Minimum safety factor, Ω, for tabulated values is 2.35.
2 Multiply tabulated values by 1.5 to obtain minimum Load and Resistance Factor Design
( LRFD) values.
3 See Figure 15.
4 Load values are for base connector only. The design professional is responsible for
checking concrete and fastener strength.
Table 133- Limit State Design( LSD) Load Data 1, 2, 3
MT-30 / 30D / 40D / 50 / 50U / 50D / 50DU / 60 / 60D
Figure 16 – MT Eccentric Channel Connection
Fx lb( kN)
Fy lb( kN)
Fz lb( kN)
My lb ft( kN m)
2,775( 12.35)
490( 2.18)
1,250( 5.57)
925( 1.26)
1 Maximum resistance factor, φ, for tabulated values is 0.55.
2 See Figure 15.
3 Load values are for base connector only. The design professional is responsible for
checking concrete and fastener strength.
Table 134- Allowable Strength Design( ASD) Load Data 1, 2, 3, 4
Fx lb( kN)
Fy lb( kN)
Fz lb( kN)
My lb ft( kN m)
2,105( 9.38)
350( 1.56)
240( 1.08)
255( 0.35
1 Minimum safety factor, Ω, for tabulated values is 2.6.
2 Multiply tabulated values by 1.5 to obtain minimum LRFD values.
3 See Figure 16.
4 Load values are for base connector only. The design professional is responsible for
checking concrete and fastener strength.
Table 135- Limit State Design( LSD) Load Data 1, 2, 3
A. MT-30 / 50 / 50 U
Fx lb( kN)
Fy lb( kN)
Fz lb( kN)
My lb ft( kN m)
2,660( 11.85)
490( 2.18)
310( 1.40)
335( 0.46)
1 Maximum resistance factor, φ, for tabulated values is 0.5.
2 See Figure 16.
3 Load values are for base connector only. The design professional is responsible for
checking concrete and fastener strength.
80 Modular Support Systems Technical Guide Edition 2 | Installation Systems Hilti, Inc. 1-800-879-8000 | en español 1-800-879-5000 | www. hilti. com | Hilti( Canada) Corporation | 1-800-363-4458 | www. hilti. ca