Modular Supports System Product Technical Guide June 2026 | Page 79

Modular Support Systems Technical Guide, Edition 2
3.0 Modular Support System
3.2.2 MT Base Connectors
MT-B-T
Description
‘ T’ shaped base plate for channel-to-concrete or channel-to-steel( X-BT / S-BT / F-BT compatible), meant to be installed with a Twist Lock and Twist Lock Bolt.
Material Specifications
Standard 1 Grade 1 F y, ksi( MPa) F u, ksi( MPa)
GB / T 700 Q235 B 34.08( 235) 53.66( 370)
1 Mechanical properties of GB / T 700 Grade Q235 B meet or exceed the mechanical properties of ASTM A1011 SS Grade 33.
Corrosion Protection
Description
Environmental Conditions
MT-B-T
Dry indoor conditions( C1)
Indoor with temporary condensation( C2)
MT-B-T OC
Outdoor, low to moderate pollution( C3 / C4- low)
Ordering Information
Description
Weight Per
Piece, lbs( kg)
Quantity
Piece( s)
Item No.
MT-B-T
1.25( 0.57)
20
2272090
MT-B-T OC 1.25( 0.57) 20 2272092 mm( in)
Figure 12 – MT Concentric Channel Connection
A. MT-30 / 50 / 60 / 40D Figure 13 – MT Eccentric Channel Connection
A. MT-50
Table 126- Allowable Strength Design( ASD) Load Data 1, 2, 3, 4
Fx Fy lb( kN) lb( kN) lb( kN)
1,400 725
225
( 6.24)( 3.23)
( 1.01)
1 Minimum safety factor, Ω, for tabulated values is 3.0. 2 Multiply tabulated values by 1.5 to obtain minimum Load and Resistance
Factor Design( LRFD) values. 3 See Figure 12. 4 Load values are for base connector only. Design professionals are responsible for checking concrete and fastener strength.
Table 127- Limit State Design( LSD) Load Data 1, 2, 3
Fx Fy
lb( kN)
lb( kN)
lb( kN)
1,890
1,005
310
( 8.42)
( 4.49)
( 1.40)
1 Maximum resistance factor, φ, for tabulated values is 0.45.
2 See Figure 12.
3 Load values are for base connector only. Design professionals are
responsible for checking concrete and fastener strength.
Table 128- Allowable Strength Design( ASD) Load Data 1, 2, 3, 4
Fx Fy
lb( kN)
lb( kN)
lb( kN)
1,450
225
725
( 6.46)
( 1.01)
( 3.23)
1 Minimum safety factor, Ω, for tabulated values is 3.0.
2 Multiply tabulated values by 1.5 to obtain LRFD values.
3 See Figure 13.
4 Load values are for base connector only. Design professionals are
responsible for checking concrete and fastener strength.
Table 129- Limit State Design( LSD) Load Data 1, 2, 3
Fx Fy
lb( kN)
lb( kN)
lb( kN)
1,960
310
1,005
( 8.72)
( 1.40)
( 4.49)
1 Maximum resistance factor, φ, for tabulated values is 0.45.
2 See Figure 13.
3 Load values are for base connector only. Design professionals are
responsible for checking concrete and fastener strength.
Fz
Fz
Fz
Fz
78 Modular Support Systems Technical Guide Edition 2 | Installation Systems Hilti, Inc. 1-800-879-8000 | en español 1-800-879-5000 | www. hilti. com | Hilti( Canada) Corporation | 1-800-363-4458 | www. hilti. ca