Description |
Environmental Conditions |
MT-CC-40D |
Dry indoor conditions( C1)
Indoor with temporary condensation( C2)
|
MT-CC-40D OC |
Outdoor, low to moderate pollution( C3 / C4- low) |
Ordering Information | |||
Description |
Weight Per
Piece, lbs( kg)
|
Quantity
Piece( s)
|
Item No. |
MT-CC-40D |
1.02( 0.47) |
10 |
2322398 |
Fx lb( kN) |
Fy lb( kN) |
Fz lb( kN) |
|
1,010
( 4.50)
|
1,685
( 7.50)
|
1,120
( 5.00)
|
1 Minimum safety factor, Ω, for tabulated values is 2.6. | ||
2 Multiply tabulated values by 1.5 to obtain minimum Load and Resistance | ||
Factor Design( LRFD) values. | ||
3 See Figure 124. | ||
4 Loading in the negative Z-direction is not recommended for this connector. | ||
|
A.
B.
|
MT-40D
MT-30 / 40D / 50 / 50U / 50DU / 50D / 60 / 60D
|
Figure 125 – Channel-to-Girder Connection | |
A. |
MT-40D |
B. |
MT-70 / 80 / 90 / 100 |
Fx lb( kN) |
Fy lb( kN) |
Fz lb( kN) |
|
1,405
( 6.26)
|
2,345
( 10.44)
|
1,560
( 6.96)
|
1 Maximum resistance factor, φ, for tabulated values is 0.55. | ||
2 See Figure 124. | ||
3 Loading in the negative Z-direction is not recommended for this connector. | ||
Fx lb( kN) |
Fy lb( kN) |
Fz lb( kN) |
|
1,010
( 4.50)
|
2,035
( 9.06)
|
1,645
( 7.33)
|
1 Minimum safety factor, Ω, for tabulated values is 2.35. | ||
2 Multiply tabulated values by 1.5 to obtain minimum LRFD values. | ||
3 See Figure 125. | ||
4 Loading in the negative Z-direction is not recommended for this connector. | ||
Fx lb( kN) |
Fy lb( kN) |
Fz lb( kN) |
|
1,405
( 6.26)
|
2,645
( 11.78)
|
2,140
( 9.53)
|
1 Maximum resistance factor, φ, for tabulated values is 0.55. | ||
2 See Figure 125. | ||
3 Loading in the negative Z-direction is not recommended for this connector. | ||