Table 335- Allowable Strength Design( ASD) Load Data 1, 5, 6, 7
Bracket
Weight lbs( kg)
L in( mm)
W lb / in( N / cm)
F1 lb( kN)
MT-BR-30 300( OC) 2
1.43
( 0.65)
11-13 / 16
( 300)
18.62
( 33.03)
220
( 1.00)
MT-BR-30 450( OC) 2
1.93
( 0.88)
17-11 / 16
( 450)
8.20
( 14.68)
145
( 0.66)
MT-BR-40 300( OC) 2
2.49
( 1.13)
11-13 / 16
( 300)
66.04
( 116.36)
780
( 3.49)
MT-BR-40 450( OC) 2
3.15
( 1.43)
17-11 / 16
( 450)
29.35
( 51.71)
520
( 2.33)
MT-BR-40 600( OC) 2
3.84
( 1.74)
23-5 / 8
( 600)
16.51
( 29.09)
390
( 1.75)
MT-BR-40 1000( OC) 2
5.64
( 2.56)
39-3 / 8
( 1000)
5.97
( 10.47)
235
( 1.05)
MT-BR-40 O4 600 OC
5.69
( 2.58)
23-5 / 8
( 600)
18.20
( 32.16)
430
( 1.93)
MT-BR-40 O4 1000 OC
7.50
( 3.40)
39-3 / 8
( 1000)
6.60
( 11.58)
260
( 1.16)
MT-BR-40D 600( OC) 3, 4
3.84
( 1.74)
23-5 / 8
( 600)
50.17
( 88.12)
1,185
( 5.29)
MT-BR-40D 1000( OC) 3, 4
5.64
( 2.56)
39-3 / 8
( 1000)
18.03
( 31.72)
710
( 3.17)
MT-BR-40D O4 600 OC
8.40
( 3.81)
23-5 / 8
( 600)
50.17
( 88.12)
1,185
( 5.29)
MT-BR-40D O4 1000 OC
12.02
( 5.45)
39-3 / 8
( 1000)
18.03
( 31.72)
710
( 3.17)
MT-BR-40D O4 1500 OC
16.49
( 7.48)
59-1 / 16
( 1500)
8.04
( 14.10)
475
( 2.11)
1 Minimum safety factor, Ω, for tabulated values is 2.5.
2 No reductions to tabulated loads need to be applied for bracket attachment to strut. The published load values are for the brackets mounted on the channels,
away from the channel edges
3 For bracket attachment to 14 gage( e. g. MT-40) vertical channel, multiply tabulated load values by 0.61. The published load values are for the brackets mounted
on the channels, away from the channel edges
4 For bracket attachment to 12 gage( e. g. MT-50) vertical channel, multiply tabulated load values by 0.66. The published load values are for the brackets mounted
on the channels, away from the channel edges
5 The loads apply only when strut profile opening is facing upward or downward.
6 The bracket’ s self-weight has been accounted for in the table load values.
7 Load values are for bracket only. Design professional is responsible for checking base material and fastener strength.