A. |
MT-100( long side) |
B. |
MT-B-GL EDB A |
Fx lb( kN) |
Fy lb( kN) |
Fz lb( kN) |
Mx lb ft( kN m) |
My lb ft( kN m) |
Mz lb ft( kN m) |
8,105( 36.07) |
1,625( 7.23) |
4,165( 18.53) |
965( 1.31) |
2,105( 2.86) |
1,215( 1.65) |
1 Tabulated values are for non-elevator applications only. | |||||
2 Minimum safety factor, Ω, for tabulated values is 2.2. | |||||
3 Multiply tabulated values by 1.5 to obtain minimum Load and Resistance Factor Design | |||||
( LRFD) values. | |||||
4 Load values are for base connector only. The design professional is responsible for | |||||
checking concrete and fastener strength. | |||||
5 See Figure 105. | |||||
Fx lb( kN) |
Fy lb( kN) |
Fz lb( kN) |
Mx lb ft( kN m) |
My lb ft( kN m) |
Mz lb ft( kN m) |
11,510( 51.20) |
2,440( 10.86) |
6,260( 27.85) |
1,450( 1.97) |
2,850( 3.87) |
1,825( 2.48) |
1 Tabulated values are for non-elevator applications only. | |||||
2 Maximum resistance factor, φ, for tabulated values is 0.64. | |||||
3 Load values are for base connector only. The design professional is responsible for | |||||
checking concrete and fastener strength. | |||||
4 See Figure 105. | |||||
Fx lb( kN) |
Fy lb( kN) |
Fz lb( kN) |
665( 2.96) |
1,300( 5.80) |
4,065( 18.09) |
1 Tabulated values are for non-elevator applications only. | ||
2 Minimum safety factor, Ω, for tabulated values is 2.1. | ||
3 Multiply tabulated values by 1.5 to obtain minimum LRFD values. | ||
4 Load values are for base connector only. The design professional is responsible for | ||
checking concrete and fastener strength. | ||
5 See Figure 106. | ||
Fx lb( kN) |
Fy lb( kN) |
Fz lb( kN) |
995( 4.43) |
1,960( 8.72) |
6,095( 27.13) |
1 Tabulated values are for non-elevator applications only. | ||
2 Maximum resistance factor, φ, for tabulated values is 0.7. | ||
3 Load values are for base connector only. The design professional is responsible for | ||
checking concrete and fastener strength. | ||
4 See Figure 106. | ||
Fx lb( kN) |
Fy lb( kN) |
Fz lb( kN) |
665( 2.96) |
1,100( 4.90) |
4,165( 18.53) |
1 Tabulated values are for non-elevator applications only. | ||
2 Minimum safety factor, Ω, for tabulated values is 2.1. | ||
3 Multiply tabulated values by 1.5 to obtain minimum LRFD values. | ||
4 Load values are for base connector only. The design professional is responsible for | ||
checking concrete and fastener strength. | ||
5 See Figure 107. | ||
Fx lb( kN) |
Fy lb( kN) |
Fz lb( kN) |
995( 4.43) |
1,655( 7.37) |
6,260( 27.85) |
1 Tabulated values are for non-elevator applications only. | ||
2 Maximum resistance factor, φ, for tabulated values is 0.70. | ||
3 Load values are for base connector only. The design professional is responsible for | ||
checking concrete and fastener strength. | ||
4 See Figure 107. | ||