Modular Supports System Product Technical Guide June 2026 | Page 133

Modular Support Systems Technical Guide, Edition 2
3.0 Modular Support System
3.2.4 MT Splice Connectors
MT-ES-40 FL / MT-ES-40 FL OC
Description
Extension splice preassembled with Fast Lock for end-toend channel connection
Material Specifications
Standard 1 Grade 1 F y, ksi( MPa) F u, ksi( MPa)
GB / T 700 Q235 B 34.08( 235) 53.66( 370)
1 Mechanical properties of GB / T 700 Grade Q235 B meet or exceed the mechanical properties of ASTM A1011 SS Grade 33.
Corrosion Protection
Description
Environmental Conditions
MT-ES-40 FL
Dry indoor conditions( C1)
Indoor with temporary condensation( C2)
MT-ES-40 FL OC
Outdoor, low to moderate pollution( C3 / C4- low)
Ordering Information
Description
Weight Per
Piece, lbs( kg)
Quantity
Piece( s)
Item No.
MT-ES-40 FL
1.79( 0.81)
14
2399669
MT-ES-40 FL OC
1.79( 0.81)
12
2399681
mm( in)
Figure 82 – Channel Splice Connection
Table 266- Allowable Strength Design( ASD) Load Data 1, 2, 3
Fx Fy
lb( kN)
lb( kN)
lb( kN)
2,105
130
1,210
( 9.38)
( 0.58)
( 5.40)
1 Minimum safety factor, Ω, for tabulated values is 2.6.
2 Multiply tabulated values by 1.5 to obtain minimum Load and Resistance Factor Design
( LRFD) values.
3 See Figure 82.
Table 267- Limit State Design( LSD) Load Data 1, 2
Fz
A. MT-30 / 50 / 60 // 50U( each channel to be same) Figure 83 – Channel Splice Connection
Fx lb( kN)
Fy lb( kN)
Fz lb( kN)
2,930( 13.05)
180( 0.81)
1,685( 7.50)
1 Maximum resistance factor, φ, for tabulated values is 0.55.
2 See Figure 82.
Table 268- Allowable Strength Design( ASD) Load Data 1, 2, 3
Fx lb( kN)
Fy lb( kN)
Fz lb( kN)
My ft lb( kN m)
4,215( 18.76)
260( 1.16)
2,425( 10.80)
475( 0.65)
1 Minimum safety factor, Ω, for tabulated values is 2.6.
2 Multiply tabulated values by 1.5 to obtain minimum LRFD values.
3 See Figure 83.
A. MT-30D / 40D / 50D / 50DU / 60D
Table 269- Limit State Design( LSD) Load Data 1, 2
Fx lb( kN)
Fy lb( kN)
Fz lb( kN)
My ft lb( kN m)
5,865
( 26.10)
360
( 1.62)
3,370
( 15.0)
665
( 0.906)
1 Maximum resistance factor, φ, for tabulated values is 0.55.
2 See Figure 83.