Modular Supports System Product Technical Guide June 2026 | Page 127

Modular Support Systems Technical Guide, Edition 2
3.0 Modular Support System
3.2.3 MT System Connectors
MT-C-GLP T A OC
Description
T-shaped adjustable angle gusset plate connector for MT-80, MT-90H, MT-90 and MT-100 girders.
Material Specifications
Description
Standard
Grade
F y, ksi
( MPa)
F u, ksi
( MPa)
MT-C-GLP T A OC
( GB / T 1591)
( Q355 B)
51.49
( 355)
68.17
( 470)
MT-C-GLP T A US OC
ASTM A1011 1
HSLAS-F
Grade 50 MOD 1
51.49
( 355)
68.17
( 470)
1 ASTM A1011 HSLAS Grade 50 MOD is an enhanced version of ASTM A1011 HSLAS
Grade 50 with Fu >= 470MPa and Fy >= 355MPa.
Corrosion Protection
Description
Environmental Conditions
MT-C-GLP T A OC
Outdoor, low to moderate pollution( C3 / C4- low)
MT-C-GLP T A US OC
Outdoor, low to moderate pollution( C3 / C4- low)
mm( in)
Ordering Information
Description
Weight Per
Piece, lbs( kg)
Quantity
Piece( s)
Item No.
MT-C-GLP T A OC
2.14( 0.97)
8
2332784
MT-C-GLP T A US OC 2.14( 0.97) 8 2487449 mm( in)
Figure 72 – MT Girder Connection
A. MT-80( long side)/ 90 / 100( long side)
Figure 73 – MT Girder Connection
Table 246- Allowable Strength Design( ASD) Load Data 1, 2, 3, 4
Fx lb( kN)
Fy lb( kN)
Fz lb( kN)
My lb ft( kN m)
Mz lb ft( kN m)
14,685( 65.33)
960( 4.28)
5,490( 24.42)
1,865( 2.53)
1,320( 1.79)
1 Minimum safety factor, Ω, for tabulated values is 2.2.
2 Multiply tabulated values by 1.5 to obtain minimum Load and Resistance Factor Design( LRFD) values.
3 See Figure 72.
4 Tabulated values are based on plates being installed in pairs.
Table 247- Limit State Design( LSD) Load Data 1, 2, 3
Fx Fy
lb( kN)
lb( kN)
lb( kN)
lb ft( kN m)
22,070
1,445
7,245
2,800
( 98.19)
( 6.43)
( 32.24)
( 3.80)
1 Maximum resistance factor, φ, for tabulated values is 0.7.
2 See Figure 72.
3 Tabulated values are based on plates being installed in pairs.
Table 248- Allowable Strength Design( ASD) Load Data 1, 2, 3, 4
Fx Fy
lb( kN)
lb( kN)
lb( kN)
lb ft( kN m)
17,240
4,355
14,100
3,945
( 76.68)
( 19.37)
( 62.71)
( 5.34)
1 Minimum safety factor, Ω, for tabulated values is 2.72.
2 Multiply tabulated values by 1.5 to obtain minimum LRFD values.
3 See Figure 73.
4 Tabulated values are based on plates being installed in pairs.
Table 249- Limit State Design( LSD) Load Data 1, 2, 3
Fz
Fz
My
My
Mz lb ft( kN m) 1,865( 2.53)
Mz lb ft( kN m)
3,050( 4.13)
A. MT-80( long side)/ 90 / 100( long side)
Fx Fy
lb( kN)
lb( kN)
lb( kN)
lb ft( kN m)
25,910
6,540
21,190
5,930
( 115.25)
( 29.11)
( 94.25)
( 8.04)
1 Maximum resistance factor, φ, for tabulated values is 0.55.
2 See Figure 73.
3 Tabulated values are based on plates being installed in pairs.
Fz My
Mz lb ft( kN m) 4,215( 5.71)
126 Modular Support Systems Technical Guide Edition 2 | Installation Systems Hilti, Inc. 1-800-879-8000 | en español 1-800-879-5000 | www. hilti. com | Hilti( Canada) Corporation | 1-800-363-4458 | www. hilti. ca