Modular Supports System Product Technical Guide June 2026 | Page 115

Modular Support Systems Technical Guide, Edition 2
3.0 Modular Support System
3.2.3 MT System Connectors
MT-C-GL OC
Description
Angle connector for MT-80( long side), MT-90, MT-90H, and MT-100 girders. Use as a base for attachment to concrete or steel( X-BT / S-BT / F-BT compatible).
Material Specifications
Standard 1 Grade 1 F y, ksi( MPa) F u, ksi( MPa)
GB / T 1591 Q355 B 51.49( 355) 68.17( 470)
1 Mechanical properties of GB / T 1591 Grade Q355 B meet or exceed the mechanical properties of ASTM A1011 SS Grade 50.
Corrosion Protection
Description
Environmental Conditions
MT-C-GL OC
Outdoor, low to moderate pollution( C3 / C4- low)
Ordering Information
Description
Weight Per
Piece, lbs( kg)
Quantity
Piece( s)
Item No.
MT-C-GL OC
2.64( 1.2)
10
2272066
mm( in)
Figure 54 – MT Single Angle Connection
Table 210- Allowable Strength Design( ASD) Load Data 1, 2, 3
Fx lb( kN)
Fy lb( kN)
Fz lb( kN)
3,070( 13.65)
2,610( 11.6)
3,070( 13.65)
1 Minimum safety factor, Ω, for tabulated values is 2.55.
2 Multiply tabulated values by 1.5 to obtain minimum Load and Resistance Factor Design
( LRFD) values.
3 See Figure 54.
Table 211- Limit State Design( LSD) Load Data 1, 2
A. MT-80( long side)/ 90 / 90H / 100
Figure 55 – MT Double Angle Connection
Fx lb( kN)
Fy lb( kN)
Fz lb( kN)
4,910( 21.83)
3,680( 16.38)
4,910( 21.83)
1 Maximum resistance factor, φ, for tabulated values is 0.55.
2 See Figure 54.
Table 212- Allowable Strength Design( ASD) Load Data 1, 2, 3
Fx lb( kN)
Fy lb( kN)
Fz lb( kN)
My lb ft( kN m)
Mz lb ft( kN m)
7,340( 32.65)
5,230( 23.27)
5,620( 25.00)
1,320( 1.79)
875( 1.19)
1 Minimum safety factor, Ω, for tabulated values is 2.2.
2 Multiply tabulated values by 1.5 to obtain minimum Load and Resistance Factor Design
( LRFD) values.
3 See Figure 55.
Table 213- Limit State Design( LSD) Load Data 1, 2
A. MT-80( long side)/ 90 / 90H / 100
Fx Fy
lb( kN)
lb( kN)
lb( kN)
lb ft( kN m)
10,690
7,360
7,980
1,870
( 47.58)
( 32.76)
( 35.49)
( 2.54)
1 Maximum resistance factor, φ, for tabulated values is 0.65.
2 See Figure 55.
Fz My
Mz lb ft( kN m) 1,140( 1.55)
114 Modular Support Systems Technical Guide Edition 2 | Installation Systems Hilti, Inc. 1-800-879-8000 | en español 1-800-879-5000 | www. hilti. com | Hilti( Canada) Corporation | 1-800-363-4458 | www. hilti. ca