Modular Support Systems Technical Supplement - USEN July 2023 | Page 8

1.0 MODULAR SUPPORT SYSTEM MT-B-GL EDB OC ( SET ) / MT-B-GL EDB A OC
MT EDB Connectors Technical Supplement Guide
Figure 8 - MT-100 Standard Connection
A . MT-100 ( long side ) B . MT-B-GL EDB OC
Table 17 - Allowable Strength Design ( ASD ) Load Data 1 , 2 , 3 , 4 , 5
F x lb ( kN )
F y lb ( kN )
F z lb ( kN )
M x lb ft ( kN m )
M y lb ft ( kN m )
M z lb ft ( kN m )
8,105
1,625
4,165
965
2,105
1,215
( 36.07 )
( 7.23 )
( 18.53 )
( 1.31 )
( 2.86 )
( 1.65 )
1 . Tabulated values are for non-elevator applications only . 2 . Minimum safety factor , Ω , for tabulated values is 2.2 . 3 . Multiply tabulated values by 1.5 to obtain minimum Load and Resistance Factor Design
( LRFD ) values . 4 . Load values are for base connector only . The design professional is responsible for checking concrete and fastener strength . 5 . See Figure 8 .
Table 18 - Limit State Design ( LSD ) Load Data 1 , 2 , 3 , 4
F x lb ( kN )
F y lb ( kN )
F z lb ( kN )
M x lb ft ( kN m )
M y lb ft ( kN m )
M z lb ft ( kN m )
11,510
2,440
6,260
1,450
2,850
1,825
( 51.20 )
( 10.86 )
( 27.85 )
( 1.97 )
( 3.87 )
( 2.48 )
1 . Tabulated values are for non-elevator applications only . 2 . Maximum resistance factor , Φ , for tabulated values is 0.65 . 3 . Load values are for base connector only . The design professional is responsible for checking concrete and fastener strength . 4 . See Figure 8 .
Figure 9 - MT-90 Standard Connection
A . MT-90 B . MT-B-GL EDB A OC
Table 19 - Allowable Strength Design ( ASD ) Load Data 1 , 2 , 3 , 4 , 5
F x lb ( kN )
F y lb ( kN )
F z lb ( kN )
665
1,300
4,065
( 2.96 )
( 5.80 )
( 18.09 )
1 . Tabulated values are for non-elevator applications only . 2 . Minimum safety factor , Ω , for tabulated values is 2.1 . 3 . Multiply tabulated values by 1.5 to obtain minimum Load and Resistance Factor Design
( LRFD ) values . 4 . Load values are for base connector only . The design professional is responsible for checking concrete and fastener strength . 5 . See Figure 9 .
Table 20 - Limit State Design ( LSD ) Load Data 1 , 2 , 3 , 4
F x lb ( kN )
F y lb ( kN )
F z lb ( kN )
995
1,960
6,095
( 4.43 )
( 8.72 )
( 27.13 )
1 . Tabulated values are for non-elevator applications only . 2 . Maximum resistance factor , Φ , for tabulated values is 0.7 . 3 . Load values are for base connector only . The design professional is responsible for checking concrete and fastener strength . 4 . See Figure 9 .
Figure 10 - MT-100 Standard Connection
A . MT-100 ( long side ) B . MT-B-GL EDB A
Table 21 - Allowable Strength Design ( ASD ) Load Data 1 , 2 , 3 , 4 , 5
F x lb ( kN )
F y lb ( kN )
F z lb ( kN )
665
1,100
4,165
( 2.96 )
( 4.90 )
( 18.53 )
1 . Tabulated values are for non-elevator applications only . 2 . Minimum safety factor , Ω , for tabulated values is 2.1 . 3 . Multiply tabulated values by 1.5 to obtain minimum Load and Resistance Factor Design
( LRFD ) values . 4 . Load values are for base connector only . The design professional is responsible for checking concrete and fastener strength . 5 . See Figure 10 .
Table 22 - Limit State Design ( LSD ) Load Data 1 , 2 , 3 , 4
2023
F x lb ( kN )
F y lb ( kN )
F z lb ( kN )
995
1,655
6,260
( 4.43 )
( 7.37 )
( 27.85 )
1 . Tabulated values are for non-elevator applications only . 2 . Maximum resistance factor , Φ , for tabulated values is 0.7 . 3 . Load values are for base connector only . The design professional is responsible for checking concrete and fastener strength . 4 . See Figure 10 .
7