Modular Support Systems Technical Supplement - USEN July 2023 | Page 15

MT EDB Connectors Technical Supplement Guide
1.0 MODULAR SUPPORT SYSTEM MT-B-EDB A OC
Description
Parallel beam wall connector for MT-90 girders .
Material Specifications
Standard 1 Grade 1 F y , ksi ( MPa ) F u
, ksi ( MPa ) GB / T 1591 Q355 B 51.49 ( 355 ) 68.17 ( 470 )
1 . Mechanical properties of GB / T 1591 Grade Q355 B meet or exceed the mechanical properties of ASTM A1011 SS Grade 50 .
Corrosion Protection
Hot-Dipped ( HDG )
MT-B-EDB A OC
Ordering Information
Description
Weight Per Piece lbs ( kg )
Quantity Piece ( s )
Item No . MT-B-EDB A OC 1.01 ( 0.46 ) 10 2353810
Figure 19 - MT Girder Connection
A . MT-90
Table 45 - Allowable Strength Design ( ASD ) Load Data 1 , 2 , 3 , 4 , 5 , 6 , 7
F x lb ( kN )
F y lb ( kN )
F z lb ( kN )
M x lb ft ( kN m )
M y lb ft ( kN m )
M z lb ft ( kN m )
1,820
1,055
3,190
80
420
2,665
( 8.11 )
( 4.70 )
( 14.21 )
( 0.11 )
( 0.57 )
( 3.62 )
1 . Tabulated values are for elevator divider beam applications only . 2 . Tabulated values must be used in conjunction with the stiffness values shown in Table 47 . 3 . Minimum safety factor , Ω , for tabulated values is 2.1 . 4 . Multiply tabulated values by 1.5 to obtain minimum Load and Resistance Factor Design
( LRFD ) values . 5 . Tabulated values represent the total allowable load on a pair of base connectors . Connectors must be installed in pairs . 6 . Tabulated values are for base connector only . Design professional is responsible for checking concrete and fastener strength . 7 . See Figure 19 .
Table 46 - Limit State Design ( LSD ) Load Data 1 , 2 , 3 , 4 , 5 , 6
F x lb ( kN )
F y lb ( kN )
F z lb ( kN )
M x lb ft ( kN m )
M y lb ft ( kN m )
M z lb ft ( kN m )
2,915
1,690
5,110
125
530
2,835
( 12.97 )
( 7.52 )
( 22.74 )
( 0.17 )
( 0.72 )
( 3.85 )
1 . Tabulated values are for elevator divider beam applications only . 2 . Tabulated values must be used in conjunction with the stiffness values shown in Table 47 . 3 . Maximum resistance factor , ϕ , for tabulated values is 0.7 . 4 . Tabulated values represent the total factored design load on a pair of base connectors .
Connectors must be installed in pairs . 5 . Tabulated values are for base connector only . Design professional is responsible for checking concrete and fastener strength . 6 . See Figure 19 .
Table 47 - EDB Connection Stiffness Data 1
Connector MT-B-EDB A k Mz lb ft / rad ( kN m / rad )
27,110 ( 36.76 )
1 . Spring stiffness values are to be used in elevator divider beam applications .
2023