METASYS - European Product Catalog 2021 | Page 137

METASYS

HVAC

BUILDING MANAGEMENT

SYSTEM CONTROL PRODUCTS

CONFIGURABLE FIELD CONTROLLERS ATC TERMINAL UNIT CONTROLLERS
TECHNICAL SPECIFICATIONS
Codes
Supply voltage Power consumption Ambient conditions
Addressing
Communication bus
BACnet MS / TP , Modbus ® and N2 through RS-485
LC-ATC1100-0 11-points Advanced Terminal unit Controller with 2 UI , 2 BI , 2 BO , 2 CO , 3 RO , FC and SA Bus , 240 VAC
LC-ATC1500-0 15-points Advanced Terminal unit Controller with 4 UI , 2 BI , 2 BO , 3 CO , 4 RO , FC and SA Bus , 240 VAC 240 VAC , 50 / 60 Hz 20 VA max
Operating 0 to 40 ° C ; 10 to 95 % RH noncondensing Storage -40 to 85 ° C ; 5 to 95 % RH noncondensing
BACnet MS / TP Valid field controller device addresses 4 – 127 ( Device addresses 0 to 3 , 117 , and 128 to 255 are reserved and not valid field controller addresses )
N2 Slave Valid field controller device addresses 1 to 255
FC Bus between the supervisory controller and field controller
SA Bus between controller , network sensors and other sensor / actuator devices , includes a 15 VDC , 210 mA power supply for bus devices
Processor
Renesas ® RX631 32-bit microcontroller , 2 MB Flash , 128 kB RAM
External memory
16 MB Flash and 8 MB RAM
Input and Output capabilities
Binary Input ( BI ):
• Dry Contact Maintained
• Pulse Counter / Accumulator Mode ( 30 Hz ) Universal Input ( UI ): User-Configurable , 3 available modes :
• Voltage Input : 0 to 10 VDC
• Resistive ( 0-10 kOhm )
• Dry-contact maintained binary Configurable Output ( CO ):
• User-Configurable , 2 available modes :
• Voltage Output : 0 to 10 VDC , 10 mA
• Triac Output : 24 VAC , 500 mA ( Externally sourced )
Input and Output count BI UI CO 5 A RO BO 10 A RO LC-ATC1100-0 2 2 2 3 2 0
24 VAC out for actuator power : 24 VAC at 500 mA 5A Relay Output ( 5A RO ):
• Single-Pole , Single-Throw , Normally Open
• 240 VAC , 5 A Resistive , 50K cycles
• 240 VAC , 0.66 FLA / 4 LRA , 50K cycles
• Shared common terminal between all 5 A RO ’ s Binary Output Triac ( BO ):
• 24 VAC or 240 VAC , 500 mA
• Externally powered
• Shared common terminal between all BO Triacs 10 A Relay Output ( 10A RO ):
• Single-Pole , Single-Throw , Normally Open
• 240 VAC , 10 A Resistive , 100K cycles
LC-ATC1500-0 2 4 3 3 2 1
Analog Input / Output resolution Analog Input 12-bit resolution , ± 1 % in the 0-10 kOhm range , ± 50 mV in the 0-10 VDC range Analog Output 15-bit , ± 200 mV in the 0-10 VDC range
... Continued ...
133 European Products Catalogue 2021