METASYS - European Product Catalog 2021 | Page 133

METASYS

HVAC

BUILDING MANAGEMENT

SYSTEM CONTROL PRODUCTS

PROGRAMMABLE CONTROLLERS VMA16 ( 32-BIT ), VMA18 , AND VMA1930 METASYS CONTROLLERS
TECHNICAL SPECIFICATION
Codes MS-VMA1615-1 32-bit , Integrated VAV Controller / Actuator / Pressure Sensor , 3 UI and 2 BO ; 24 VAC ; FC and SA Bus
32-bit , Integrated VAV Controller and Actuator , 3 UI , 3 BO , and 2 CO ; 24 VAC ; FC Bus , and SA Bus
MS-VMA1626-1 ( No DPT ) 32-bit , Integrated VAV Controller and DPT , 3 UI , 3 BO , and 2 CO ; 24 VAC ; FC Bus , and SA Bus
MS-VMA1628-1
( No Actuator ) MS-VMA1630-1 32-bit , Integrated VAV Controller / Actuator / DPT , 3 UI , 3 BO , 2 CO ; 24 VAC ; FC and SA Bus
32-bit , Integrated VAV Controller and Actuator , 3 UI , 3 BO , and 2 CO ; 24 VAC ; FC Bus , and SA Bus ,
MS-VMA1656-1 Integrated Ball Valve Linkage ( No DPT ) 32-bit , Integrated VAV Controller and Actuator , 3 UI , 3 BO , and 2 CO ; 24 VAC ; FC Bus , and SA Bus ,
MS-VMA1826-1 with 8-9in TSTAT Port , Recommended for use as a replacement for VMA1440 ( No DPT ) 32-bit , Integrated VAV Controller / Actuator / DPT , 3 UI , 3 BO , 2 CO ; 24 VAC ; FC and SA Bus , with
MS-VMA1832-1
8-pin TSTAT Port . Recommended for use as a replacement for VMA1410 , VMA1415 , or VMA1420
32-bit , Integrated VAV Controller / Actuator / Pressure Sensor - DPT , 3 UI and 3 BO , 2 CO , 24 VAC , MS-VMA1930-0 and SA Bus , Includes 6-pin Sensor Port for use with TE-7xx Series Non-Communicating Sensors and two Ethernet Ports for BACnet / IP Communications
Communications Protocol MS-VMA16xx-x , MS-VMA18xx-x BACnet MS / TP , N2
MS-VMA1930-0 BACnet / IP
Engines Supported MS-VMA16xx-x , MS-VMA18xx-x All Models
SNC , SNE , NAE55 , NAE85 , ODS , OAS ( MS-VMA1930-0 supports R9 . 0 or later versions of these MS-VMA1930-0 engines ) Power Requirement 24 VAC ( nominal , 20 VAC minimum / 30 VAC maximum ), 50 / 60 Hz , Safety Extra-Low Voltage ( SELV ) Power Consumption
10 VA typical , 14 VA maximum
Note : VA ratings do not include any power supplied to the peripheral devices connected to Binary Outputs ( BOs ) or Configurable Outputs ( COs ), which can consume up to 12 VA for each BO or CO , for a possible total consumption of an additional 60 VA ( maximum ).
Ambient Conditions Operating 0 ° C to 50 ° C
Storage -40 ° C to 70 ° C
Terminations
MS-VMA1615-x , MS-VMA1626-x , Inputs / Outputs : 6.3 mm Spade Lugs MS-VMA1628-x , MS-VMA1630-x , FC Bus , SA Bus , and Supply Power : 4-Wire and 2-Wire Pluggable Screw Terminal Blocks
MSVMA1656-x FC Bus and SA Bus Port : RJ-12 6-Pin Modular Jacks
Inputs / Outputs , SA Bus , and Supply Power : 6.3 mm Spade Lugs
MS-VMA1826-x , MS-VMA1832-x N2 / FC Bus : Pluggable Screw Terminal Block TSTAT Modular Port : RJ-45 8-Pin Modular Jack Inputs / Outputs : 6.3 mm ( 1 / 4 in .) Spade Lugs
MS-VMA1930-0 SA Bus and Supply Power : 4-Wire and 2-Wire Pluggable Screw Terminal Blocks
SA Bus Modular Ports : RJ-12 6-Pin Modular Jacks
... Continued ...