was lower when compared with the average
office building in Malaysia. However, we believe
that JKR Complex still has the potential to
achieve an energy-efficient office building BEI
if saving measures proposed in this article are
implemented.
The breakdown of the overall energy
consumption of the buildings shown in Figure 5
above shows the highest (66.14%) was consumed
by the air-conditioning and ventilation system
and the second highest was the internal lighting
(21.53%) followed by office equipments and
domestic usage (7.5%) and the elevators (3.65%).
Energy Saving Measures
The recommended energy saving measures, ‘with
cost’ and ‘without cost’, in mid-year 2016 until
June 2017, to reduce the existing BEI of 127 kWh/
m 2 /year, are shown in the two tables below.
After the ‘without cost’ cost-saving measures
have been taken and those in item 2 of the ‘with
cost’ section have been made, the BEI readings
of JKR Complex may be reduced from a BEI 127
reading to an even lower BEI reading if the cost
savings for items 1 and 3 in the ‘with cost’ section
are executed.
In June 2017, the JKR Building Maintenance
Facility Branch in collaboration with the Building
Sector Energy Efficiency Project (BSEEP)
agreed to carry out item no. 4 - to install the
Online Monitoring System. The objective of this
installation is to monitor the energy consumption
of each block at the JKR Complex and to provide
1) ENERGY SAVING MEASURES WITHOUT COST
No.
RECOMMENDED ENERGY MEASURES
1
2
3
4
Air Conditioner at Prayer Room/Surau Block F to operate only
from 12 pm to 5 pm.
Operating time adjustment of air conditioning system
Implementation of energy saving programmes:
Awareness Programme
Role of Level Officer to switch off the lights during the
afternoon break
Periodic inspection
Turning off 80% of indoor lighting during lunch break.
TOTAL
2) ENERGY SAVING MEASURES WITH COST
No.
RECOMMENDED ENERGY MEASURES
1
2
3
4
6
18
Replacement of 2 chiller units and 3 cooling units in the
cooling tower
Replacement of 4,763 existing lighting units in Block F to LED
energy-efficient lamps.
Replacement of air ducting at Block F
Online monitoring system for energy consumption of each block
at JKR Complex
TOTAL
VOL
- SEPTEMBER
2017
VOL 71
55 JULY
JUNE
2013
ESTIMATED YEARLY
SAVINGS (kWh)
936.00
10,731.00
15,876.00
72,915.14
100,458.14
ESTIMATED YEARLY
SAVINGS (kWh)
182,520.00
233,348.00
224,238.00
640,106.00