Observe that the through penetration firestops have been installed
in such a manner that the required movement can be achieved.
Compare the installed firestop system with the approved submitted
details
Observe a reasonable degree of workmanship, which would indicate
compliance with the specified designs
Deficient installations must immediately be corrected and then re-
inspected before concealment
As mentioned before also, in NBC 2016, under Annexure E,
subsection E7, Fire and Life Safety Audit recommendation is
highlighted. However, the qualification and approval of firestop
inspectors are yet to be described.