Concrete Floors / Walls |
CLICK CATEGORY INFO BELOW : |
||||
Penetrating Item ( s ) F-Rating T-Rating L-Rating W-Rating Product |
System Number [ Similar FM Approved System ] |
Blank Openings
Metallic Penetrants
|
|||
NEW |
NON-METALLIC PIPES IN CONCRETE FLOORS / WALLS * ( CONTINUED )
Max . 1-1 / 2 ” PP ( SDR 7.4 or 11 ). Aquatherm Greenpipe PP-R ( SDR 7.4 or 11 ), Bluepipe PP-RCT ( SDR 9 or 11 ) Niron PP-RCT ( by Nupi Americas ( SDR 7.3 , 9 , or 11 ), Aquatechnik PP-RCT ( SDR 7.4 or 11 ) and Uponor PP-RCT ( SDR 9 or 11 ) ( c , v ) 50 Pa
Max . 2 ” PVC or CPVC ( c ) ( AS = 3 / 4 ” to 1-1 / 4 ”)
Max . 2 ” PVC or CPVC ( c ) ( sleeved ) ( AS = 1 / 2 ” to 1 ”)
Max . 2 ” PVC , CPVC ( SDR 13.5 ) ( AS = 9 / 16 ”)
Max . 2 ” PVC or CPVC ( SDR 13.5 ) ( AS = 5 / 8 )
Max . 2 ” ABS , PVC , CVPC , FRPP , or max . 1 ” PEX ( c , v ) ( AS = 5 / 16 ”)
Max . 2 ” PVC , CPVC , PEX , RNC ( c , v ) ( AS = 0 ” to 5 / 8 ”)
Max . 6 ” PVC or CPVC ( c , v ) ( AS = 0 ” to ½ ” for pipe 4 ” and smaller ) ( AS = 0 ” to ¾ ” for 6 ” pipes )
Max . 3 ” PVC or CPVC ( c , v ) ( AS = 1 / 4 ”)
2 Hr ◼
CP 680-P CP 680-PX
F-B-2075
1 or 2 Hr ◼ FS-ONE MAX W-J-2019
4 Hr FS-ONE MAX W-J-2057
2 Hr ◼ CP648E / 1 ” W-J-2069
2 Hr ◼ CP648E / 1 ” W-J-2070
2 Hr CP 648E / 1 ” W-J-2071
2 Hr ◼ ◼ FS-ONE W-J-2072
4 Hr ◼ CP 643N W-J-2091
1 Hr ◼ CP 648E / 1-3 / 4 ” W-J-2101
|
Non-Metallic Pipes *
Cables / Cable Trays
Insulated Pipes
Miscellaneous Electrical ( Busway )
Miscellaneous Mechanical / Ducts
Mixed Penetrating Items *
Blank Openings
Metallic Penetrants
Non-Metallic Pipes *
Cables
Cable Trays
Insulated Pipes
Miscellaneus Electrical ( Busway )
Miscellaneous Mecahnical / Ducts *
Mixed Penetrating Items *
|
Framed ( Gypsum ) Walls
Concrete Floors / Walls
|
||
|
Max . 9 ” PVDF ( c , v ) ( sleeved ) ( AS = 0 ” to ½ ”)
Max . 2 ” PVC or CPVC ( c , v ) ( Optional sleeve )
( AS = 1 / 4 ” to 11 / 16 ”)
Max . 12 ” FRP pipe ( c , v ) ( sleeved ) ( AS = 0 ” to ½ ”)
Max . 4 ” PVC , CPVC , or ABS ( c , v ) ( angled pipe )
|
2 Hr ◼ CP 648E / 1-3 / 4 ” W-J-2107
1 or 2 Hr FS-ONE MAX W-J-2108
2 Hr ◼ CP 648E / 1-3 / 4 ” W-J-2115
|
Blank Openings
Metallic Penetrations
Non-Metallic Pipes *
Cables
Insulated Pipes
Miscellaneous Mechanical / Duct Penetrations
|
Wood-Framed Floors |
||||||||||||||||||
|
NEW
NEW
|
( AS = 0 ” to ¾ ”)
Max . 12 ” PVC or CPVC ( c , v ) ( AS = 0 ” to ½ ”)
Max . 2 ” ENT ( c ) ( AS = 1 / 4 ” to ¾ ”)
Max . 2 ” ENT ( c ) ( AS = 3 / 16 ” to 5 / 16 ”)
Max . 6 ” PVC , CPVC , or max . 4 ” ABS ( c , v ) ( AS varies ) Option : PEX and 2 ” insulation
Max . 1-1 / 2 ” PVC , CPVC , RNC , or 1 ” PEX ( closed ) ( one or more ) ( AS = 0 ” to 1 ”)
Max . 4 ” diameter bundle of max . 1 ” PEX ( closed ) ( AS = 0 ” to 1 ’)
Max . 4 ” PP ( SDR 11 ), Max . 8 ” Aquatherm Greenpipe ( SDR 7.4 or 11 ), Max . 8 ” Aquatherm Bluepipe ( SDR 9 or 11 ), Max . 4 ” PP Polystar CT-White , or max 125mm Fusiotherm ( c ), Max . 4 ” PEX , Max . 4 ” Niron PP-RCT ( SDR 7.3 , 9 , or 17 ) ( c , v ), Max . 8 ” Niron PP-RCT ( SDR 7.3 or 11 ) ©, Max . 8 ” Aquatecknik PP-RCT ( SDR 7.4 or 11 ), Max . 8 ” Uponor PP-RCT ( SDR 7.3 or 11 ) ( AS = 0 ” to ½ ”) UL only
Max . 1 ” PEX ( bundled ) ( c , v ) through CP 653 Speed Sleeve
Max . 2 ” ENT ( one or more ) through CP 653 Speed Sleeve
Max . 3 / 8 ” Single or bundled pneumatic tube ( AS = 0 ” to 1 ”)
Max 1 / 2 ” Single or bundled Dura-line Microduct ( AS = 0 ” to 1 ”)
Max 1 / 2 ” Single or bundled Dura-line Microduct ( AS = 0 ” to 1 ”)
Cable bundle ( various cables ) in flexible nylon raceway ( PVC sleeve optional ) ( AS = 0 ” to 3 ”)
Cable bundle ( various cables ) in flexible nylon raceway ( steel sleeve optional ) ( AS = 0 ” to 3 ”)
Max . 2 ” PP , Aquatherm Greenpipe ( SDR 7.4 or 11 ), Aquatherm Bluepipe ( SDR-9 or 11 ), Napsys PVC , ( c , v ) ( AS = 0 ” to 5 / 8 ”) 50 Pa Canada only
|
1 or 2 Hr ◼ CP648S W-J-2205
1 or 2 hr FS-ONE MAX W-J-2206
1 or 2 hr FS-ONE MAX W-J-2207
2 Hr ◼
CP 648E / 1-3 / 4 ” w / Ret Collar
W-J-2218
2 Hr Speed Sleeve W-J-2229
2 Hr Speed Sleeve W-J-2230
2 Hr FS-ONE MAX W-J-2236
2 Hr ◼ FS-ONE MAX W-J-2237
2 Hr ◼ CP 643N with CP 618 W-J-2238
3 Hr CP 618 W-J-2241
2 Hr Firestop Plug W-J-2242
2 Hr ◼ CP 643N W-J-2247
|
Mixed Penetrating Items *
Metallic Penetrations
Non-Metallic Pipes *
Cables
Insulated Pipes
Miscellaneous Mechanical / Duct Penetrations
Mixed Penetrating Items *
Bottom of Wall ( BW-S Series )
Continuity Head-of- Wall ( CJ-D Series )
Floor-to-Floor ( FF-D Series )
Floor-to-Wall ( FW-D Series )
Intertek Series ( ASTM E 1966 )
Head-of-Wall ( HW-D Series )
Head-of-Wall ( HW-S Series )
Wall-to-Wall ( WW-D Series )
Wall-to-Wall ( WW-S Series )
Perimeter Fire Barrier Joints ( Curtain Wall ) – ASTM E2307
|
Joints Steel-Framed Floors |
|||||||||||||||||