Firestop Inspection Guidebook English 2024 | Page 12

5 . LISTED FIRESTOP SYSTEMS
A UL / CUL listed firestop system contains complete information about a tested system as per ASTM and / or Canadian standards . It shows a typical assembly of all involved components / parameters with their detailed description . It mentions overall fire rating of the testing system along with a few possible variations of different parameters , the size range of different penetrating components , plus different possible materials . It also provides a list of all applicable product ranges for the given assembly .
Fire rating of the system as per ASTM E814
Min . required thickness of Floor or wall assembly
A valid type of components with details like annular space requirement
Max . size of all the allowed / valid penetrations along with valid material
Min . required thickness and density of packing material like mineral wool
Min . thickness of the sealant / firestop product to be used All Hilti products that can be used with this assembly
Fig . 5 : Sample UL listing of through-penetration system
A UL system gives you information on different variations for a particular assembly / system . It is a complete document and considered credible among all the countries following UL / ASTM standards . One should first check the availability of a tested system for a particular arrangement onsite . If it is not available , only then the contractor should use the manufacturer ’ s engineering judgment ( EJ ) services .
Inspection Guidebook 12 / 28