Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 96

3. Stairs Details Fire escape stairs, depending upon the requirement of Division 8 through 17 of this Chapter, shall be in accordance with the following table and subsequent paragraphs. Table 6: DIMENSIONAL CRITERIA FOR FIRE ESCAPE STAIRS DIMENSIONS PARTICULARS Minimum widths Minimum horizontal dimension any landing of platform Maximum rise Minimum tread, exclusive of nosing 60 cm clear between rails 60 cm 23 cm 23 cm Solid, 13 mm diameter perforation permitted None None Tread construction Winders (spiral) Risers Maximum height between landings Headroom, minimum 3.66 m 2.00 m Door or casement windows 61 cm by 1.98 m or double hung windows 76.20 cm by 91.44 cm clear Not over 30.50 cm above floor; steps if higher Swinging stair section permitted 45 per unit* access by door; 20 if access by climbing over window rail Access to escape Level of access opening Discharge to ground Capacity number of persons 4. Arrangement and Protection of Openings Fire escape stairs shall be so arranged that they will be exposed by the smallest possible or window and door openings. There shall be no transom over doors. Every opening, any portion of which is in the limits specified below, shall be completely protected by approved fire doors or metal-frame wired glass windows in the same manner as provided for outside stairs and outside ramps. 5. Access a. Access to fire escape stairs shall be provided in accordance with the table in para “A” (3) of this Section and the general provisions of paragraph “K” Section 10.2.5.2 of this IRR. b. Where access is by way of double windows, such windows shall be 80