Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 436

C. Tagging of Serviced Fire Extinguishers Whenever any person duly qualified by the Department of Trade and Industry or its equivalent services a fire extinguisher, a tag shall at least indicate: 1. The month and year the services are performed. 2. The chemical name and formula of the contents. 3. The type of extinguisher serviced. 4. The name, address, contact details and certificate of registration number of the servicing firm. SECTION 10.5.3.3 SERVICING AND MAINTENANCE A. Maintenance and servicing of fire extinguishers shall be performed periodically, but at least once every twelve (12) months, after each use, or when an inspection shows that the need is obvious. B. Hydrostatic test shall be performed every five (5) years. SECTION 10.5.3.4 CERTIFICATE OF COMPETENCY A. No person shall engage in the manufacture, sale or servicing of fire extinguishers without a certificate of competency issued by the BFP. B. All salesmen shall possess working knowledge on the following matters, among others, as a requirement for the issuance of certificate of competency: 1. Principles of fire fighting; 2. Types of extinguishers and their capabilities; 3. Selection and matching the extinguishers to the hazard, the environment and the user’s capability; 4. Number and distribution of extinguisher for a particular hazard; 5. Operation and maintenance of extinguishers; and 6. Health and operational safety considerations. C. All technicians engaged in the manufacture, sale or servicing of fire extinguishers shall possess, in addition to those required of salesmen per para “B” above, working knowledge on standards in the following: 1. Hydrostatic testing; 420