SECTION 10.4.5.3 STORAGE A. The manufacture of explosives or blasting agents shall be prohibited unless such manufacture is authorized by law. B. Explosives, including special industrial high explosive materials, shall be stored in magazines that meet the requirement of the Fire Code and this IRR. C. Smoking, matches, open flames, spark-producing devices, firearms and combustible materials shall be prohibited inside or within fifteen meters (15 m) from the magazine. D. The land surrounding magazines shall be kept clear or brush, dried grass, leaves, trash and debris for a distance of at least fifteen meters (15 m). E. Magazines shall be kept locked except when being inspected or when explosives are being placed therein or removed therefrom. F. Magazines shall be kept clean, dry and free of grit, paper, empty packages and rubbish. G. Magazines shall not be provided with other than approved artificial heat or light. Approved electric safety flashlights or safety lanterns may be used. H. Blasting caps, electric blasting caps, detonating primers and primed cartridges shall not be stored in the same magazine with other explosives. I. Packages of explosives shall not be unpacked or repacked in a magazine nor within forty-five and eight-tenths meters (45.8 m) of a magazine or in close proximity to other explosives. Opened packages of explosives shall be securely closed before being returned to a magazine. J. Magazines shall not be used for the storage of any metals, tools nor any commodity except explosives, blasting agents and oxidizers used in compounding blasting agents. The quantity of blasting agents and oxidizers shall be included when computing the total quantity of explosives for determining distance requirements. K. Floors of magazines shall be securely fastened in place and shall be capable of withstanding the loads imposed. L. The roofs and exterior sides of building-type magazines shall be made of concrete materials with fire resistance rating of two (2) hours. M. Magazines shall be ventilated to minimize dampness and heating of stored explosives. Ventilation openings shall be screened with 14 mesh, 342