i. A fast-closing, “quarter turn” manual shutoff valve shall be provided at a fast-fill station upstream of the breakaway device, readily accessible to the person dispensing natural gas. j. A self-closing valve shall be provided on the inlet of the compressor that shuts off the gas supply to the compressor. 14. Installation of Electrical Equipment Fixed electrical equipment and wiring, within areas specified in Table 28 below, shall comply with same table and shall be installed in accordance with NFPA 70, National Electrical Code®. Electrical equipment on internal combustion engines shall be installed in accordance with NFPA 37, Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines. Table 28: ELECTRICAL INSTALLATIONS IN CNG SERVICE STATIONS Location Division or Zone Extent of Classified Area Containers (other than mounted fuel supply 2 Within 3 m of container containers) Area containing compression and ancillary equipment Outdoors 2 Up to 4.6 m from equipment Indoors 2 Up to 4.6 m from equipment Dispensing equipment Outdoors 1 Inside the dispenser enclosure Outdoors 2 From 0 to 1.5 m from the dispenser Indoors 1 Inside the dispenser enclosure Entire room, with adequate Indoors 2 ventilation Outdoors Discharge from relief valves 1.5 m in all directions from the point 1 or vents source Beyond 1.5 m but within 4.6 m in all 2 directions from point of discharge Valves, flanges of screwed None Unclassified fittings Discharge from relief valves within 15 degrees of the line of 1 4.6 m discharge Exception: Listed dispensers shall be permitted to be installed using classified areas in accordance with the terms of the listing. 326