Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 319

be allowed provided that the container is properly secured and the dispensing apparatus is designed for such liquefied gas use. Exception: compressed gas containers with an internal volume less than five thousandth cubic meter (0.005 m3) may be used in a horizontal position. 15. The handling of compressed gas containers shall comply with the following requirements: a. Carts and trucks. Containers shall be moved using an approved method. Where containers are moved by hand cart, hand truck or other mobile device, such carts, trucks or devices shall be designed for the secure movement of containers. Carts and trucks utilized for moving compressed gas containers outdoors shall be so designed that the containers will be secured against dropping or otherwise striking against each other or other surfaces. b. Lifting of containers. Ropes, chains or slings shall not be used to suspend compressed gas containers unless such containers have been designed for such handling. Valves of compressed gas containers shall not be used for lifting. 16. Compressed gas containers, equipment and devices used for the storage, handling and transportation of compressed gases shall be of approved type. 17. Approved containers, equipment or devices are those covered with appropriate certification from its manufacturers and/or certifying authority concerned. 18. Electrical installations and equipment shall conform to the provisions of the Philippine Electrical Code, equipment manufacturers’ instruction and/or other applicable international standards as deemed necessary. 19. Proper lighting, including emergency lights shall be provided to illuminate fire protection appliances and operating facilities such as walkways, control valves, gauges, and similar devices or servicing facilities for the compressed gas 20. Lighting equipment and facilities shall be of explosion proof type. 21. Container design and construction shall be maintained as follows: a. Compressed gas containers shall be designed and fabricated in accordance with the specifications of the PSME Boiler and Pressure Vessels Code or shall comply with appropriate standards of the DOE and DTI. 303