Philippine Electrical Code. Suitable means shall be taken to protect the system against corrosion, including corrosion caused by stray electric currents. b. Containers and systems containing cryogenic fluids shall be equipped with lightning protection when installed outside the building/ structure. 4. Valves and Accessory Equipment a. All valves and equipment shall be suitable for the intended use at the temperature of the application and shall be designed for not less than the maximum pressure and the minimum temperature to which they may be subjected, maintaining a safety factor and four (4) to one (1). b. Shutoff valves shall be provided on all container connections. Shutoff valves shall be located as close as practicable to the container. c. All liquids and vapor connections on flammable cryogenic fluid containers, except relief and gauging connections over twelve millimeters (12 mm) pipe size, shall be equipped with check valves, or remotely controlled automatic quick-closing valves, and shall remain closed except during operating periods. d. Shutoff valves shall be installed in the piping system as needed to limit the volume of liquids discharged in the event of piping or equipment failure. Relief valves shall be installed between shutoff valves in all pipelines. e. All inlet and outlet connections, except relief valves, liquid level gauging devices, and pressure gages on any container, shall be labeled to designate whether they are connected to vapor or liquid space. C. Warning Labels 1. Warning labels and signs shall be posted visibly from any direction of approach on cryogenic containers and equipment. In addition, they shall be properly marked with the name of the specific cryogenic fluid, manufacturer/ supplier and contact details. 2. The name of the specific cryogenic fluid shall be conspicuously affixed at the entrances to locations where they are stored, handled, used, or dispensed, and at such other locations as may be designated by the City/Municipal Fire Marshal having jurisdiction. 296