Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 307

vi. Safety relief valves shall normally be mounted in a vertical position and shall not be subjected to low temperature except when operating. e. Containers shall be provided with substantial concrete or masonry foundations, or structural steel supports on firm concrete or masonry foundations. Foundations and supports shall be of a material and design to withstand the low temperature effects of cryogenic fluid spillage. Structural steel supports, above forty-six centimeters (46 cm) in height, or flammable cryogenic fluid container shall be protected with protective coating having a fire- resistance rating of two (2) hours. f. Horizontal containers shall be so mounted on foundations as to permit expansion and contraction. Every container shall be supported to prevent the concentration of excessive loads on the supporting portion of the shell. That portion on the container in contact with foundation or saddles shall be protected against corrosion. g. Secure anchorage or elevation of container shall be provided in an area that may be subjected to flooding. h. Storage containers, piping, valves, regulating equipment, and other accessories shall be protected against physical damage and against tampering. i. Containers shall be secured as may be necessary to prevent shifting or upset. 2. Containers shall be equipped with drainage, dikes and walls having the following conditions: a. The area surrounding a container for cryogenic fluids shall be diked to prevent accidental discharge of fluids thereby endangering adjacent containers, buildings and equipment, adjoining property or reaching waterways. b. Drainage shall be provided at a slope of not less than one percent (1%) away from the container towards an impounding basin or an appropriate means of disposal having a capacity equal to the container being served. This termination area and the route of the drainage system shall be so located that a fire occurring in drainage system will not seriously endanger adjacent containers or property. c. Where diked areas are utilized to provide the required protection, the following shall apply: 291