Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 294

iii. No vessel or craft shall be allowed to moor or berth at any fuel docks serving a marine services station, except during fueling operations. iv. No construction, maintenance, repair or reconditioning work involving the use of open flames or arcs or spark-producing devices shall be performed at any marine service station facility or within fifteen meters (15 m) of the dispensing facilities including piers, wharves, or floats. The City/Municipal Fire Marshal having jurisdiction may grant permission in writing to make repair provided no fueling is done at the pier, wharf, of float during the course of such emergency repairs. v. All electrical equipment must comply with the latest edition of the Philippine Electrical Code as it applies to wet, damp and hazardous location. Clearly identified emergency switches readily accessible in case of fire at any dispensing unit shall be provided on each main float and at the shore approach to the pier, wharf or floating dock, to shut off power to all pump motors from any individual location and reset only from the master switch. Each switch shall be identified by an approved sign: "EMERGENCY PUMP SHUTOFF". The master switch shall be set in the "OFF" position before closing a marine service station. Pressure system shall incorporate with each turbine an indicator light illuminated when the turbine is running. Said lights shall be visible from the shore approach and from the dispenser location and suitably identify the system served. vi. Smoking or open flames shall be prohibited within fifteen meters (15 m) of fueling operations. "NO SMOKING" signs shall be posted conspicuously within the premises. Such signs shall have letters not less than centimeters (10 cm) in height on a background of contrasting color. vii. Boat owners or operators shall not offer their craft for fueling unless the tanks being filled are properly vented to dissipate fumes to the outside atmosphere. viii. There shall be prominently displayed at the face of each wharf, pier of float at such elevation as to be clearly visible from the decks of marine craft being fueled, a sign or signs with letters not less than eight centimeters (8 cm) in height in a background of contrasting color bearing the following or equivalent wording: WARNING NO SMOKING - STOP ENGINE WHILE FUELING. SHUT OFF ELECTRICITY. DO NOT START ENGINE UNTIL AFTER BELOW-DECK SPACES ARE VENTILATED 278