Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 227

2. Exits from mezzanine floors in aircraft storage or servicing areas shall be so arranged that the maximum travel to reach the nearest exit from any point on mezzanine shall not exceed twenty three meters (23 m). Such exits shall lead directly to a properly enclosed stairwell discharging directly to the exterior or to a suitably cut-off area or to outside stairs. B. Signs Exits signs shall be provided above all doors and exit ways in accordance with Section 10.2.5.12 of this IRR. SECTION 10.2.16.5 SPECIAL PROVISIONS FOR GRAIN ELEVATORS A. In grain elevators, there shall be at least one (1) stair tower from storeys below the floor of exit discharge to the floor of exit discharge and from the floor of exit discharge to the top floor of the working house enclosed on a dust tight non-combustible shaft. B. Noncombustible doors of the self-closing type shall be provided at each floor landing. C. An exterior stair or basket ladder type fire escape accessible from all working levels of the head house that provides access to the top of the adjoining structure and that provides a continuous path to the means of egress. D. An exterior stair or basket ladder type fire escape accessible from all working levels of the head house that provides passage to the ground level. DIVISION 17. MISCELLANEOUS STRUCTURES Any building or structure occupied for purposes not covered by Division 8 through 17 of this IRR shall have exits and related safeguards in accordance with the fundamental principles of this Chapter, and shall comply with the following provisions where applicable. SECTION 10.2.17.1 TOWERS A. Any tower utilized for such purposes as observation, signaling, either as an independent structure or on top of a building, shall be permitted to have a single stairway or ramp exit if all of the following conditions are met: 1. The tower is of such size as not to be subject to occupancy by more than twenty five (25) persons at any floor level. 2. The tower shall not be used for living or sleeping purposes. 211