DIVISION 16. STORAGE OCCUPANCIES SECTION 10.2.16.1 GENERAL STORAGE OCCUPANCIES A. Occupancy Load The occupant load, in number of persons for whom means of egress and other provisions are required, shall be determined on the basis of the maximum probable population of the space under consideration. B. Exit Details 1. Types of Exits Means of egress for storage occupancies shall be restricted to the following types: a. Doors b. Stairs and Smokeproof Enclosures c. Horizontal Exits d. Ramps e. Slide Escapes 2. Capacity of means of egress The capacity of means of egress shall be determined in accordance with Section 10.2.5.2, para ā€œCā€ of this IRR. 3. Number of Exits a. Every building or structure used for storage and every section thereof considered separately shall have at least two (2) separate means of egress, as remote from each other as practicable. Exception: In rooms or spaces of less than one thousand three hundred ninety four square meters (1,394 m 2 ) gross area where less than ten (10) persons may normally be present, at least one (I) means of egress shall be provided for any person employed therein. b. Every storage area shall have access to at least one (1) means of exit which can be readily opened, not subject to locking at any time that any persons are therein, and not dependent on any power-operated doors except where the design of the power- operated doors may be opened manually in case of power failure to permit exit travel. 207