Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 206

3. Exceptions for Class C stores In any Class C store, openings may be unprotected between street floor and balcony or mezzanine. B. Interior Finish 1. Interior finish of exits of all stores shall be Class A and Class B in accordance with Section 10.2.6.3 of this IRR. 2. In any Class A or Class B store, interior finish of the ceiling shall be Class A or Class B in accordance with Section 10.2.6.3 of this IRR, unless completely protected by an approved, supervised automatic fire suppression system in accordance with Section 10.2.6.5 of this IRR, in which case Class C interior finish may be used in any Class A or Class B store, interior finish of the' walls shall be Class A, Class B or Class C in accordance with Section 10.2.6.3 of this IRR. 3. In any mercantile occupancy, exposed portions of structural members complying with the requirements for heavy timber construction may be permitted. Laminated wood shall be delaminate under the influence of heat. 4. In a Class C store, interior finish shall be Class A, B or C in accordance with Section 10.2.6.3 of this IRR. C. Alarm Systems Class A and Class B stores shall be provided with an automatic and manual fire alarm system in accordance with Section 10.2.6.4of this IRR. D. Automatic Sprinkler Protection Approved, supervised automatic sprinkler system protection shall be installed in accordance with Section 10.2.6.5 of this IRR in all mercantile occupancies as follows: 1. Throughout all mercantile occupancies three or more storeys in height. 2. Throughout all mercantile occupancies exceeding one thousand one hundred fifteen square meters (1,115 m 2 ) in gross area. 3. Throughout floor below the street floor having an area exceeding two hundred thirty two square meters (232 m 2 ) when used for the sale, storage or handling of combustible goods and merchandise. E. Hazardous Areas 1. An area used for general storage, boiler or furnace rooms, fuel 190