Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 201

travel in different directions (no common path of travel). 3. All vertical opening shall be enclosed. C. Occupant Load 1. For purposes of determining required exits, the occupant load of mercantile buildings or parts of building used for mercantile purposes shall not be less than the following: a. Street floor, one (I) person for each two and eight-tenths square meters (2.8 m 2 ) gross floor area. In stores with no street floor as defined in Division 2 of this Chapter, but with access directly from the street by stairs or escalators, the principal floor at the point of entrance to the store shall be considered the street floor. In stores where due to difference in grade of streets on different sides, there are two (2) or more floors directly accessible from the street (not including alleys or similar back streets), each such floor shall be considered a street floor for the purpose of determining occupant load. b. Due to differences in grade of streets on different sides, two or more floors directly accessible from streets (not including alleys or similar back streets) exist; each such floor is permitted to be considered a street floor. The occupant load factor is one person for each 3.7 square meters of gross floor area of sales space. c. Sales floors below the street floor: same as street floor. d. Upper floors, used for sale: one (1) person for each five and six tenths square meters (5.6 m 2 ) gross floor area. e. Floor or sections used only for offices, storage, shipping and not open to the general public: one (1) person for each nine and three-tenths (9.3) square meters gross floor area. f. Floors or sections used for assembly purposes: occupant load determined in accordance with Division 8 of this Chapter. g. Covered Walls: one (1) person for each two and eight-tenths square meters (2.8 m 2 ) gross floor area. 2. Where any required egress capacity from a balcony or mezzanine passes through the room below, that required capacity shall be added to the required egress capacity of the room below. 185