Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 192

5. Extinguishing Requirements a. All buildings shall be protected throughout by an approve, supervised sprinkler system except in buildings where all guest sleeping rooms or guest suites have a door opening directly outside at the street or grade level or exterior exit access arranged in accordance with Section 10.2.5.2 of this IRR in buildings up to and including three (3) storeys in height. b. Listed quick response or listed residential sprinklers shall be used throughout guest rooms and guest room suites. c. Portable fire extinguishers shall be installed in accordance with Section 10.2.6.7 of this IRR. 6. Subdivision of Building Spaces a. In buildings not protected by an approved, supervised automatic sprinkler system, each hotel guest room, including guest suites, and dormitory rooms shall be separated from other guest rooms or dormitory rooms by walls and floors having fire resistance ratings of not less than one (1) hour. b. In buildings protected throughout by an approved, supervised automatic sprinkler system, each hotel guest room, including guest suites, and dormitory room shall be separated from other guest rooms or dormitory rooms by walls and floors constructed a fire barriers having fire resistance ratings of not less than one half (½) hour. 7. Hazardous Areas a. Any room containing high pressure boilers, refrigerating machinery, transformers, or other service equipment to possible explosion shall not be located directly under or directly adjacent to exits. All such rooms shall be effectively cut off from other parts of the building as specified in Section 10.2.6.8 of this IRR. b. Every hazardous area shall be separated from other parts of the building by construction having a fire-resistance rating of at least one (1) hour and communicating openings shall be protected by approved automatic or self-closing fire doors, or such area shall be equipped with automatic fire suppression system. Where a hazard is high as determined by the City/Municipal Fire Marshal having jurisdiction, both fire-resistive construction and automatic fire suppression system shall be used. Hazardous areas include, but are not limited to: 176