Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 181

SECTION 10.2.11.3 PROTECTION A. Protection of Vertical Opening 1. Any vertical opening shall be enclosed or protected. Exception no. 1: Unprotected vertical openings in accordance with Section 10.2.6.2 of this IRR shall be permitted. Exception no. 2: In sleeping quarters smoke compartments, unprotected vertical openings shall be permitted in accordance with the conditions of 10.2.6.2of this IRR, provided that the height between the lowest and highest finished floor levels does not exceed seven meters (7 m). The number of levels shall not be restricted. Sleeping quarters subdivided in accordance with this section shall be permitted to be considered as part of the communicating space. The separation shall not be required to have a fire resistance rating. B. Interior Finish Interior finish shall be Class A or Class B C. Detection, Alarm and Communication Systems 1. Detention and correctional occupancies shall be provided with a fire alarm system in accordance with Section 10.2.6.4 of this IRR, except as modified by the succeeding paragraphs. 2. Initiation of the required fire alarm system shall be by manual means in accordance with Section 10.2.6.4 of this IRR, by means of any required detection devices or detection systems, and by means of waterflow alarm in the sprinkler system. Exception No. 1: Manual fire alarm boxes shall be permitted to be locked, provided that staff is present within the area when it is occupied and staff has keys readily available to unlock the boxes. Exception No. 2: Manual fire alarm boxes shall be permitted to be located in a staff location, provided that the staff location is attended when the building is occupied and that the staff attendant has direct supervision of the sleeping area. 3. Occupant notification shall be accomplished automatically in accordance with Section 10.2.6.4 of this IRR, a positive alarm sequence shall be permitted. Exception: any smoke detectors required by this chapter shall be permitted to be arranged to alarm at a constantly attended location only and shall not be required to accomplish general occupant 165