Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 176

3. Approved, supervised sprinkler system shall be provided throughout all hospitals, nursing homes, and residential-custodial care facilities. Replenishment of water supplies shall be strictly considered in the design. Quick-response sprinklers shall be required in smoke compartments containing patient sleeping rooms. 4. Approved, supervised sprinkler system shall be in accordance with the requirements of Section 10.2.6.5 of this IRR. 5. In light hazard occupancies, required automatic fire suppression systems shall be in accordance with Section 10.2.6.5 of this IRR for systems and shall be electrically interconnected with the fire alarm system. The main automatic fire suppression control valve shall be electrically monitored so that at least a local alarm will sound when the valve is closed. 6. If the fire suppression system is an automatic sprinkler, its piping serving no more than six (6) sprinklers for any isolated hazardous area, may be connected directly to a domestic water supply system having a capacity sufficient to provide six (6) liters per minute per square meters of floor area throughout the entire enclosed area. As outside-screw- and-yoke shutoff valve shall be installed in an accessible location between the sprinklers and the connection to the domestic water supply. 7. Portable fire extinguishers shall be provided in all institutional oc- cupancies in accordance with Section 10.2.6.5 of this IRR. G. Hazardous Areas Any hazardous area shall be segregated and protected in accordance with Section 10.2.6.8 of this IRR. Hazardous areas include, but are not limited to the following: Boiler and heater rooms Laundries Kitchens Repair shops Handicraft shops Employee locker rooms *Soiled linen rooms *Paint shops *Rooms or spaces, including shops, used for the storage of combustible supplies and equipment in quantities deemed hazardous by the Chief, BFP or his duly authorized representative. Trash collection rooms Gift shops Those areas marked by asterisk (*) shall be both separated and provided with automatic fire suppression system. SECTION 10.2.10.4 BUILDING SERVICE EQUIPMENT A. Air Conditioning, Ventilating, Heating, Cooking and Other Service 160