square meters (11.1 m 2 ) gross floor area in health care sleeping departments and not less than one (1) persons for each twenty two square meters (22.3 m 2 ) of gross floor area of inpatient health care treatment departments. Gross floors areas shall be measured within the exterior building walls with no deductions. SECTION 10.2.10.2 EXIT DETAILS A. Number and Types 1. Exits shall be restricted to the following permissible types; a. Doors leading directly outside the building b. Stairs and smoke-proof enclosures c. Ramps d. Horizontal exits e. Exit Passageways 2. At least two (2) exits of the above types, remote from each other, shall be provided for each floor or fire section of the building. 3. Elevators constitute a supplementary facility, but-shall not be counted as required exits. B. Capacity of Exits The capacity of means of egress shall be in accordance with Section 10.2.5.2 para ā€œCā€ of this IRR. C. Access to Exit 1. Every aisle, passageway, corridor, exit discharge, exit location and access shall be in accordance with Section 10.2.5.2 of this IRR, except as modified in the succeeding paragraphs of this subsection. 2. Travel distance shall comply with the following: a. Between any room door intended as exit access and an exit shall not exceed thirty (30) meters; b. Between any point in a room and an exit shall not exceed forty six (46) meters; c. Between any point in a health care sleeping room or suite and an exit access door of that room or suite shall not exceed fifteen (15) meters. 153