Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 155

C. Interior Finish Interior finish shall be Class A in corridors, stairways and other means of egress and may be Class B or Class C elsewhere, in accordance with the provisions of Section 10.2.6.3 of this IRR. D. Fire Alarm System 1. Approved fire alarm facilities capable of being manually operated in accordance with Section 10.2.6.4 of this IRR shall be provided in every educational building. 2. In building provided with automatic fire suppression system the operation of the system shall automatically actuate electrical school fire alarm system. E. Automatic Fire Suppression System Every portion of educational buildings below the floor of exit discharge shall be protected with complete automatic sprinkler protection in accordance with Section 10.2.6.5 of this IRR. F. Hazardous Areas An area used for general storage, boiler or furnace rooms, fuel storage, janitors closets, maintenance shops including woodworking and painting areas, laundries and kitchen shall be separated from other parts of the building with construction having not less than a one-hour fire resistance rating, and all openings shall be protected with self-closing fire doors, or such area shall be provided with automatic fire suppression system. Where the hazard is high as determined by the Chief, BFP or his duly authorized representative, both the fire resistive separation and automatic fire suppression system shall be provided. G. Cooking equipment Cooking equipment shall be protected by automatic kitchen hood fire suppression in accordance with NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations. SECTION 10.2.9.6 BUILDING SERVICE EQUIPMENT A. Elevators 1. An elevator shall not constitute required means of exit. 2. When an educational occupancy is more than three (3) storeys and equipped with automatic elevators, one or more elevators shall be designed and equipped for fire emergency use by firefighters, as 139