Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 134

building service equipment pierces the partitions shall be closed. Transfer grills, whether equipped with fusible links, release dampers or not, shall not be used in these partitions. C. Doors in Smoke Partitions 1. Doors in required smoke partitions shall be of a swinging type and shall have a protection rating of at least twenty (20) minutes. 2. Any glass panels in doors in smoke partitions shall be of transparent wired glass mounted in steel frames. 3. Doors in smoke partitions shall be automatically self-closing. 4. Doors in smoke partitions shall close the opening with only the clear- ance for proper operation under self-closing. 5. Doors in smoke partitions shall be without undercuts, louvers, or grills. SECTION 10.2.6.10 FIRE DOORS A. Any fire door, installed in accordance with the requirements of this Chapter shall be of an approved type. The fire resistance rating of any fire door shall be as measured in accordance with the appropriate internationally accepted standard. Each fire door shall be appropriate for the location in which it is installed. B. Any swinging fire door and any door in stair enclosure walls designed to prevent the spread of fire shall be provided with approved positive latching means to hold it in the closed position against the pressure of expanding fire gases. DIVISION 7. BUILDING SERVICE EQUIPMENT SECTION 10.2.7.1 UTILITIES A. Equipment using gas and related gas piping shall be in accordance with NFPA 54, National Fuel Gas Code, or NFPA 58, Liquefied Petroleum Gas Code, as the case may be. B. Electrical wiring and equipment shall be in accordance with the Philippine Electrical Code. C. Cooking equipment shall be protected by automatic kitchen hood fire Suppression in accordance with NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations. 118