Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 107

L/min) per linear meter of water curtain, measured horizontally around the opening. 8. The water curtain shall operate automatically from thermal responsive elements of fixed temperature type so placed with respect to the ceiling (floor) opening that the water curtain comes into action upon the advance of heat toward the escalator opening. 9. Every automatic exhaust system, including all motors, controls and automatic water curtain system shall be supervised in an approved manner, similar to that specified for automatic sprinkler system supervision. D. Spray Nozzle Methods 1. Under the conditions specified in paragraph "B" (1) above, escalator openings may be protected by the nozzle method, consisting of a combination of an automatic fire or smoke detection system and a system of high velocity water spray nozzle meeting the following requirements: a. Spray nozzles shall be in the open type and shall have a solid coni- cal spray pattern with discharged angles between forty-five (45) and ninety (90) degrees. The number of nozzles, their discharge angles and their location shall be such that the escalator opening between the top of the wellway housing and the treadway will be completely filled with the dense spray on operation of the system. b. The number and size of nozzles and water supply shall be sufficient to deliver a discharge of one and four-tenths (1.4) liters of water per square meter per second through the wellway, area to be figured perpendicular to treadway. c. Spray nozzles shall be so located as to effectively utilize the full advantage of the cooling and counterdraft effect. They shall be so positioned that the center line of spray discharge is as closely as possible in line with the slope of the escalator, not more than an angle of thirty (30) degrees with the top slope of the wellway housing. Nozzles shall be positioned, also so that the center line of discharge is an angle of not more than an angle of thirty (30) degrees with the top slope of the wellway housing. d. Spray nozzles shall discharge at a minimum pressure of 172 KPa. Water supply piping may be taken from the sprinkler system, provided that in so doing an adequate supply of water will be available for the spray nozzles and the water pressure at the sprinkler farthest from the supply riser is not reduced beyond the required minimum. 91