Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 105

c. The entire area, including all communicating floor levels, is sufficiently open and unobstructed so that it may be assumed that a fire or other dangerous condition in any part will be immediately obvious to the occupants of all communicating levels and areas; d. Exit capacity is sufficient to provide simultaneously for all occupants of all communicating levels and areas, all communicating levels in the same fire area being considered as a single floor area for purposes of determination of required exit capacity; e. Each floor level, considered separately, has at least one-half of its individual required exit capacity provided by an exit or exits leading directly out of that area without traversing another communicating floor level or being exposed to the spread of fire or smoke therefrom; and f. All requirements of this Chapter with respect to interior finish, protection of hazards, construction and other features are fully observed, without waivers, except openings in floors of educational, healthcare, and detention and correctional occupancies shall be enclosed as required in Divisions 9, 10 and 11 of this Chapter, respectively. 3. Each floor opening, as specified in paragraph A (1) of this Section shall be enclosed by substantial walls having fire resistance not less than that required for stairways, paragraph A (4) hereof, with approved fire doors at windows provided in openings therein, all so designed and in- stalled as to provide complete barrier to the spread of fire or smoke through such openings. 4. The enclosing walls of floor openings serving stairways or ramps shall be so arranged as to provide a continuous path of escape including landings and passageways, in accordance with Section 10.2.5.4 of this IRR providing protection for person using the stairway or ramp against fire or smoke therefrom in other parts of the building. Such walls shall have fire resistance rating as follows: a. New buildings four storeys or more in height - two (2) hours fire resistance rating. b. New buildings below four storeys - One (1) hour fire resistance rating. B. Special Provisions for Escalator Openings Any escalator shall have its floor opening enclosed or protected as required for other vertical openings, except in building completely protected by approved, supervised sprinkler system in accordance with 89