Finishes Manufacturer's Product Guide Vol. 1 | Page 56
Skyway™ Ceiling Clouds Type I & II
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
Core Fiberglass Density: 6 - 7 pcf.
Recycled Content: For fiberglass, 52 percent pre-consumer and 5 percent post-consumer recycled content.
Fiberglass Facings: 1/8 inch thick layer of 16 - 20 pcf molded fiberglass on face and back.
Core Thickness: 1-1/4 inch.
Core Thickness: 2-1/4 inches.
Width: 24-48 inches and custom.
Length: 24-120 inches and custom.
Corners: Square.
Edges: Square.
Finish Type and Color: Soft Texture White.
Finish Type and Color: Foundations White
Finish Type and Color: Subtle Texture White or Custom.
Finish Type and Color: New Dimensions White or Custom.
Edge Treatment: Resin hardened.
Finish: Manufacturer, pattern and color as selected: applied directly over face and edges of panel and returned
to back of panel to provide full finished edge; corners fully tailored.
Mounting Type: Standard, direct attachment to resin spots with self-drilling acoustical hangers or grid (by
others).
Flammability (ASTM E 84): Panel components shall have a Class “A” rating per ASTM E 84.
Resistivity To Heat Or Cold: R-factor of 4.16 per inch of thickness.
Acoustical Performance: Values below are for panels mounted in accordance with ASTM C 423 (Type D5
Mounting) and vary by panel thickness and finish
a.
Noise Reduction Coefficient (NRC) for 1-1/8 inch thickness: 0.90.
b.
Noise Reduction Coefficient (NRC) for 2-1/8 inch thickness: 1.10.
PART 3 - EXECUTION
3.1
INSTALLATION
A.
Verify wet work such as plastering and concrete is complete and dry. Verify building is enclosed and under standard
occupancy conditions (60 - 85 degrees F and not more than 70 percent relative humidity) prior to start of installation.
Commencement of installation constitutes Installer’s acceptance of surfaces and conditions.
B.
Install products in accordance with manufacturer’s written instructions and in proper relationship with adjacent
construction, including the following:
1.
C.
For adhesive installation to substrate, provide temporary support to prevent panel slippage. Note: Impaling clips
are designed to help hold panels in place until adhesive dries.
Touch-up, repair or replace damaged units until satisfactory results are obtained.
END OF SECTION