Product Data Sheet
RESIST PANELS
PART 1 GENERAL
1.1 Work in this section shall be subject to drawings, general
conditions, schedules, addenda and other contract
documents.
1.2 The extent of the acoustical panels is shown on the
drawings and in the schedules.
1.3 Submit _______ (select quantity) samples of each type of
acoustical panel as shown on the drawings and in schedules
and include appropriate technical information including test
data and maintenance instructions. Submit __________
(select quantity) fabric selector cards from manufacturer’s
standard finishes, or designer specified finishes.
1.4 Acoustical panels shall be installed according to
manufacturer’s recommendations and instructions.
1.5 Installation of acoustical panels shall not begin until all wet
work (plastering, concrete, etc.) is completed and dry.
Building shall be properly enclosed and under standard
occupancy conditions (temperature of 60-85°F and not
more than 70% relative humidity) before installation begins.
1.6 The contractor shall be responsible for the examination
and acceptance of all surfaces and conditions prior to the
acoustical panel installation.
1.7 Substitutions or changes will only be permitted by prior
approval by the architect.
PART 2 MATERIALS
2.1 Acoustical wall panels shall be: Resist Acoustical Wall Panels
as manufactured by Conwed Designscape|Wall Technology
800 Gustafson Road, Ladysmith, WI 54848.
Phone (800) 932-2383, fax (800) 833-4798
2.2 Acoustical Panels shall be constructed of a composite core
construction of dimensionally stable, rigid, resilient fiberglass
of 6-pcf density. Thickness (choose one): 1-1/8”, 2-1/8 or
custom ____________ (specify).
2.3 Sizes: ______ width and _______ high or as shown on
drawings. Standard maximum size is 48” wide x 120”
high (nominal). Custom or larger sizes available; consult
manufacturer. Panels are to be manufactured according
to field dimensions supplied by the installing contractor.
Standard tolerances are ± 1/16” in width and length.
2.4 Edge profile shall be: Square, &F