Breaches, prosecutions and infringements Winter 2020 energysafe issue 58 Rating Cause Clause description 10 AS/NZS 5601.1 2013 Clause 5.2.6 DESIGN OF CONSUMER PIPING – Flexibility of piping 4 Non-compliances Breaches » Pipe expansion and flexibility calculations should refer to AS4041, clause 5.2.7 and 5.7.5. » Pipe work installed in roof has no allowance for expansion. » Internal straight run of pipe work in excess of 30 metres. 11 AS/NZS 5601.1 2013 FLUE INSTALLATION – Support independent of gas appliance Breaches Clause 6.8.2 4 Non-compliances » Flues were not securely fixed and supported with brackets independently of the appliance. 12 AS/NZS 5601.1 2013 Breaches Clause 5.2.6 FLUE TERMINALS – Location of flue terminals of balanced flue, room-sealed, fan-assisted or outdoor appliances 4 Non-compliances » Flue termination distance issue; not in accordance with Fig 6.2 (h) and Fig 6.2 (g). » Gas heater flue terminal installed close to the ground. » Flue termination has duct work installed next to it. 13 AS/NZS 5601.1 2013 GAS APPLIANCE CONNECTION – Means of isolation Breaches Clause 6.6.3 4 Non-compliances » Isolation valve not accessible for operation on inlet connection of an appliance in accordance with Table 6.4. » Missing or no access to appliance isolation valve and regulator. 22