EnergySafe Magazine Spring 2017, issue 48 | Page 10

10 Electrical Q&A  Your electrical questions answered! Compiled by ESV’s Electricity Technical Advisor, John Stolk EnergySafe continues its regular series featuring some of the questions that ESV receives on a range of electricity installation issues, some of them relating to gas installations. Also provided are the answers together with references to the Acts, Standards, Regulations and Clauses that apply to them. Question Answer Standard Clause Can someone tell me the clause number for cables to be clipped every 300mm? The Wiring Rules do not specify a set distance between supports, but requires cables to be installed to minimise damage to the sheathing and insulation with the provision of supports, continuous or at appropriate intervals suitable for the mass of the cable. AS/NZS 3000:2007 Clause 3.9.3 Does an outbuilding (i.e a shed 3m away from the main building) always require a distribution board? No, there is no requirement for an outbuilding to have a sub board installed. AS/NZS 3000:2007 Clause 2.3.4.1 (a)(i) and (ii) AS/NZS 3000:2007 Clause 2.5.3 AS/NZS 3000:2007 Clause 1.5.11.2 and 3.9.8 I would put one in regardless but clause 2.3.4.1(b)(i) seems to imply it is not necessarily. Clause 2.3.4.1 of AS/NZS 3000:2007 specifies the requirements if a switchboard is installed. Hey guys, I’m trying to find a clause number that specifically states ovens/ cooking appliances have to be on their own dedicated circuit. Can anyone help or point me in the right direction? The Wiring Rules do not specify that a cooking appliance requires to be installed on its own dedicated circuit. The manufacturer could have that requirement within their installation instructions. Boys having a discussion at work regarding RCDs. One is of the opinion that the minimum size that can feed a 40A RCD is 6mm. The other is saying the cable size is depending on maximum demand of the circuit breakers being feed by that 40a RCD. The cable supplying an RCD shall have a current carrying capacity not less than the maximum current rating of the RCD. When an air cooling unit is added to an existing gas fired Hydronic ducted heating unit (i.e. Air Smart system), does the electrical supply to both units have to be altered to comply with the isolation requirements similar to a split air-conditioning systems? Yes. Air-conditioning systems incorporating a compressor shall be provided with a lockable isolating switch installed adjacent to the unit, which isolates all parts of the system including ancillary equipment, from the same location. Where the manufacturer requires a part of the system to be connected by a plug and socket at the internal unit, the isolating switch installed at the external unit shall control the socket outlet supplying the internal unit. The cable supplying a 40 amp RCD can have a current carrying capacity of less than 40 amps if:- » » overload protection device supplying the RCD is less than 40 amps, or » » overload protection devices on the load side of the RCD total less than 40 amps » » the current carrying capacity of the conductor may be sized to the overload production.