EnergySafe Magazine May 2014, issue 35 | Page 7

07 For all the latest energy safety news visit www.esv.vic.gov.au May 2014 energysafe issue 35 Requirements for builders’ construction supplies As a result of a number of complaints received by ESV in relation to builders’ construction supplies, random audits were recently conducted of builders’ construction supplies connected or ready to be connected to supply. The results of these audits were extremely disappointing, with most builders’ construction supplies identified as having defects. ESV is reaffirming the requirements for builders’ construction supplies prior to a major audit of the trade to ensure compliance. The audits revealed that most building construction supplies had varying degrees of noncompliance. The following represents a summary of the common defects identified: »» Installations where the support structure was identified as not securely fixed or unstable after excavation »» Additional mechanical protection not provided in areas where the ground was excavated around conduits that contained live, unprotected cables »» Enclosures installed that were not fit for purpose, such as domestic metering enclosures installed without being enclosed within the building or structure as required by the manufacturer’s instructions »» Underground cable drawings/maps showing t