EnergySafe Magazine May 2014, issue 35 | Page 17

17 For all the latest energy safety news visit www.esv.vic.gov.au May 2014 energysafe issue 35 Installation of DC cables Can I install DC sub-array cable within a roof space of a building where the arrays are located on different sections of the roof? Yes, DC cables must be installed compliant with section 3 of AS/NZS 3000:2007 Selection and Installation of Wiring Systems. When installing solar roof tiles, can I install the isolating switch on the fascia board? Yes, where DC cables are installed within a structure (such as a roof space) and are not controlled by an isolating device, the protection method of Cause 3.9.4.4 (a) & (b) of AS/NZS 3000:2007 must be used. To minimise the risks of DC arcs occurring between conductors, double insulation between positive and negative conductors shall be maintained within heavy duty (HD) enclosures where installed within a structure. In locations where it can reasonably be expected that cables are subject to mechanical damage, the protection method of AS/NZS 3000:2007 Clause 3.9.4.4 (a) & (b) must be used, eg. cables installed in an accessible roof space or cable enclosed in walls. Solar boosted equipment Is the DC supply from the solar panels for The DC supply from the solar array can be